4.6.2 Hydraulic integration
A mixer must be installed when combining a calorifier with
underfloor heating. A minimum circulation water quantity
is not required.
4.6.2.1 Cascades
As a basic principle, the Hoval TopTronic should per-
form cascade control. This ensures an environmentally
and product-friendly method of operation. However, if an
external cascading strategy is planned and boiler perfor-
mance control is carried out, frequent cycles should be
avoided (at least 12 minutes burner running time).
Please observe the notes in the configuration
documents of the responsible Hoval sales
company with respect to the appropriate hy-
draulic switches!
Example:
UltraGas
®
(125 - 1150)
Gas boiler with
- water heating,
- Wall distributor with separate return
- 1 mixed heating circuit and water heating to high-
temperature return
- 1 mixed heating circuit to low-temperature return
Hydraulic schematic BCST050
Please close unused connections tightly
Important information:
• The example schematics merely show the
basic principle and do not contain all in-
formation required for installation. Instal-
lation must be carried out according to the
conditions on-site, dimensioning and local
regulations.
•
With underfloor heating, a flow temperature
limit thermostat must be installed.
• Shut-off devices to the safety equipment
(pressure expansion tank, safety valve,
etc.) must be secured against unintentional
closing!
• Install sacks to prevent single-pipe gravity
circulation!
• An automatic air vent (AAV) must be in-
stalled before the shut-off valve. This is not
supplied by Hoval.
Dies ist ein
unerlaubter Weg!
Gehen Sie einen
Schritt zurück oder
löschen Sie dieses
Shape!
Sie haben die
Möglichkeit ein
neues Shape zu
nehmen!!!
hovhovalh
hovalhova
alhovalho
UltraGas
(125-650)
NT
HT
NT
HT
P
Dies ist ein
unerlaubter
Weg!
Gehen Sie
einen Schritt
zurück oder
löschen Sie
dieses Shape!
Sie haben die
Möglichkeit ein
neues Shape
zu nehmen!!!
hovhovalhoval
hovalhovalhov
alhovalhovalho
valhovalhovalh
ovalhovalhoval
hovalhovalhov
alhovalhovalho
valhovalhovalh
ovalhovalhoval
hovalhovalhov
alhovalhovalho
valh
WW
T
KW
SF
SLP
RS-T
AF
TopTronic T
RS-T
1
HT
NT
B1
VF2
T
T
MK2
M
YK2
B1
VF2
T
T
MK2
M
YK2
VF1
T
T
MK1
M
YK1
SV
AAV
UltraGas
®
(125-1150)
S-T
Room station
AF
Fresh air sensor
VF1
Flow sensor 1
VF2
Flow sensor 2
SF
Calorifier heater sensor
B1
Flow temperature limit thermostat
(if required)
SV
Safety valve
AAV
Automatic venting
MC1
Pump mixer circuit 1
MK2
Pump mixer circuit 2
SLP
Calorifier loading pump
YK1
Actuator mixer 1
YK2
Actuator mixer 2
HT
High temperature
NT
Low temperature
TTE
Fig. 21
29
4 217 215 / 00
INSTALLATION