4.
Installation
4.1
Safety instructions
CAUTION
Cutting injuries as a result of sharp edges.
Handle parts of the casing carefully and
avoid contact with sharp edges.
4.2
Requirements on the boilerhouse
§
Regarding the building specifications for boil
-
er rooms, regulations specific to the state or
country are to be observed.
Regarding the ventilation of boiler rooms, reg-
ulations specific to the state or country are to
be observed.
!
CAUTION
Gas boilers are not allowed to be installed
in rooms in which halogen compounds oc-
cur and can get into the combustion air (e.g.
washrooms, drying rooms, hobby rooms,
hairdressers).
!
CAUTION
Halogen compounds can be created, for ex-
ample, by cleaning and degreasing agents,
solvents, glue and bleaches
Always make sure there is an adequate supply of com-
bustion air to the boiler room.
This contributes to correct function of all the firing devices
that are operated there, and provides oxygen for the op-
erating personnel to breathe.
Make sure there is an adequate supply of fresh air to the
boiler room, according to local regulations.
4.2.1 Room air dependent installation
Binding values for the size of supply air openings are not
generally specified in the relevant regulations. It is merely
required that no partial vacuum in excess of 3 N/m
2
oc-
curs.
4.2.2 Room air independent installation
Variant using "Connection for direct combus-
tion air supply" or "Motorised air intake damp-
er" (optional):
•
When configuring the intake tube, comply
with the following:
- If the air inlet at the facade is near
a noise sensitive place (window of
bedroom, terrace etc.), we recommend
to use a sound absorber at the
direct combustion air inlet.
- The air intake opening must be freely ac-
cessible and have a protective grating or
possibly wind protection equipment.
- Always keep the air inlet clear (leaves,
snow, ...)
- Do not store any chemicals or poisonous
substances in the vicinity of the air inlet
- Do not install the air inlet adjacent to ex-
tractor hood openings or other air extrac-
tion equipment.
24
4 217 215 / 00
INSTALLATION