Condensing unit
■
Lifting the condensing unit with a crane:
– Use 2 straps at least 8 m in length.
■
Lifting the condensing unit with a forklift:
– Transport to the installation site: Lift the unit under the pallet.
– Unloading from the pallet: Guide the forklift tines into the large rectangular
openings under the device.
■
Observe the installation instructions provided.
7.2 Storage
If you do not install the unit immediately:
■
Remove the packaging film to avoid water vapour condensation.
■
Store the unit in a dry, dust-free room.
■
Keep the storage temperature between – 30 °C and + 50 °C.
■
Avoid too long storage periods. After a storage period of more than 1 year:
– Check that the bearings of the fans move smoothly before installing the unit.
7.3 Requirements for the installation site
TopVent
®
unit
■
Comply with the minimum and maximum distances.
■
Only secure the unit to ceilings with sufficient load-bearing capacity.
■
All air inlet and air outlet openings must be freely accessible. The supply air jet
must be free to spread out unhindered.
■
The access panels in the unit must be freely accessible.
■
Clearance of at least 0.9 m is required for maintenance work around the
heating/cooling section and, if applicable, the supplementary heater.
X/2
X
Y
Z
Size
6
9
Unit clearance X
min.
m
12
14
max.
m
23
31
Distance from ceiling Z
min.
m
0.3
0.4
Mounting height Y
min.
m
4
5
max.
1)
m
Approx. 9…25
1) The maximum mounting height varies depending on the boundary conditions (for values,
see table of heat outputs or calculation with the 'HK-Select' selection program)
Table 20: Minimum and maximum distances
Fig. 11:
Lifting with a crane
Fig. 12:
Lifting with a forklift
27
TopVent
®
TP
Transport and installation
4 218 024-en-04