5.2 Electrical connection
TopVent
®
TP
Unit type
TP…6K
TP-9…K
TP-9-M
Supply voltage
V AC
3 × 400
Permitted voltage tolerance
%
± 5
Frequency
Hz
50
Connected load
kW
3.6
Current consumption max.
A
5.9
Series fuse
A
13.0
Table 7: TopVent
®
TP electrical connections
Electric heating coil
6S
9R
9S
Connected load
kW
14
14
28
Current consumption max.
A
20
20
40
Series fuse
A
20
20
40
Table 8: Electric heating coil electrical connections
ERQ250 condensing unit
Unit type
TP…6-K
TP…9-K
TP-9-M
Supply voltage
V AC
3 × 400
3 × 400
Permitted voltage tolerance
%
± 10
± 10
Frequency
Hz
50
50
Connected load
kW
13.5
2 × 13.5
Current consumption max.
A
21.6
2 × 21.6
Series fuse
A
25
2 × 25.0
Inrush current
A
74
2 × 74.0
Table 9: Daikin ERQ250 condensing unit electrical connections