5.3 Info menu recirculation unit
■
Navigate to the next page with .
Info menu 01/06
RECU 61
Supply air temp.:
Actual value 32.5
Setpoint 32.7
Operating mode RECU_H
Door contact closed
10:18 28.07.17
Displays:
■
Current supply air temperature
■
Supply air temperature setpoint
■
Current operating mode of the unit
■
Position of door contact
Info menu 02/06
RECU 61
Heating valve 100%
Cooling valve 0%
Air-Injector 10%
Return temp. 40
10:18 28.07.17
Displays:
■
Position of the heating valve
■
Position of the cooling valve
■
Position of the Air-Injector
0 % = Vertical air supply
100 % = Horizontal air supply
■
Return temperature
Info menu 03/06
RECU 61
Supply air
temperature alarms
Min limit < 5.0
Max limit > 60.0
10:18 28.07.17
Displays:
■
Lower limit of supply air temperature
■
Upper limit of supply air temperature
An alarm is triggered if the supply air
temperature is outsides these limits.
Setting the limits:
■
Navigate to the limit with .
■
Set value with .
■
Confirm with
.
Info menu 04/06
RECU 61
Pumps DO /DI
Heating pump On /On
Cooling pump Off/Off
Supply air fan 0%
10:18 28.07.17
Displays:
■
Heating pump: switching command and
feedback
■
Cooling pump: switching command and
feedback
■
Current air flow rate
(in % of the nominal air flow rate)
I
nfo menu 05/06
REMU 01
Air-Injector
Room temp. start point
summer shifting 40.0
Min. limit discharge
direction: 0.0%
10:18 28.07.17
Displays:
■
Start point for summer shifting:
From this room temperature the twist is
reduced and the air is blown more vertically
downwards. The cooling effect becomes
more strongly felt.
■
Min limit discharge direction:
A minimum value limiting the downward
discharge angle of the air flow can avoid
draughts in the occupied area.
Adjusting the air distribution:
■
Navigate to the input field with
.
■
Set value with .
■
Confirm with
.
Info menu 06/06
RECU 61
Operating hours
Filter maintenance
signal: 3000h
Current: 230h
Reset:
0
10:18 28.07.17
Displays:
■
Operating hours for maintenance
reminder
■
Time that has elapsed since the last filter
exchange
Setting the maintenance reminder:
■
Navigate to the input field with
.
■
Set value with .
■
Confirm with
.
Reset elapsed time to 0:
■
Navigate to '
Reset
' with .
■
Set the value to '
1
' with .
■
Confirm with
.