4.2 Setting the room temperature setpoint
Example:
The room temperature setpoint is to be set to 22 °C.
Precondition: The
User
operator level is active (password entry see section 2.6).
O
verview i 01/01
ZONE Mode SA2
REMU 01 02
RECU 61 62
10:18 ! 28.07.17
■
In
Overview
(with the cursor on the '
O
')
press the key.
■
The
Main menu
appears.
Main menu 2/5
Overview
Operating menu
Weekly calendar
Date/Time
Logout
■
In
Main menu
, navigate to '
Operating
menu
' with .
■
Confirm with
.
O
perating menu 01/05
ZONE
REMU Operating mode: 7
1=ST/2=SA1/3=SA2
4=REC1/5=REC/6=EXT
7=AUTO
10:18 28.07.17
■
Navigate to page 2 of the operating
menu with .
Operating menu 02/05
ZONE
Room temp. setpoints:
Day
21.0
Cool prot. 15.0
Overheat prot. 27.0
10:18 28.07.17
■
On page 2, navigate to the input field for
room temperature setpoint day with .
■
Set the value '
22.0
' with .
■
Confirm the entry with
.
Operating menu 02/05
ZONE
Room temp. setpoints:
Day 22.0
Cool prot.
15.0
Overheat prot. 27.0
10:18 28.07.17
■
Back to
Main menu
: Press .
or
■
Back to
Overview
: Press .
12
TopTronic
®
C
System control for TopVent
®
Operating examples
4 216 689-en-01