background image

16

Immersion Heaters

Immersion heaters

General

All work should be carried out by suitably qualified
personnel.

Heaters must be handled with care and stored in
dry conditions.

Adequate withdrawal space must be provided to
allow the removal of the heater assembly.

Carefully remove all protective packaging and
visually inspect unit for any transit damage.

All prevailing rules, regulations and bylaws in force
at the time and place of installation must be
observed.

Heaters must only be immersed in the fluid they
are designed to heat.

The introduction of alternative fluids even in small
concentrations for purposes such as sterilising
may cause serious damage to the heater and will
invalidate the warranty.

Any modification not carried out by Heatex Limited
or its approved  agent will invalidate certification
and warranty.

Precautions must be taken to prevent damage to
enclosure seals.

Installation

The heater should be securely fixed in position and
all terminal connections checked for tightness
before energising.

The installed orientation of horizontally mounted
heaters must be such that any thermostats or
other temperature sensors are uppermost.

Sealing gaskets must be undamaged.

The terminal box must not be used for tightening
heater into tank or  vessel.

Electrical Supply Connection

Refer to wiring diagram on page 17.

The cable entry or gland plate is  positioned on the
side of the terminal box.

Before connection ensure that the supply
corresponds with that specified on the rating label.

Ensure that the sizes and types of cables to be
used are suitably rated for the load and temperature
of the unit.

Each heater must be protected by a suitably rated
over current device.

The cables must enter the heater terminal box via
a suitable cable gland to maintain the IP rating and
be fitted by a qualified person.

Earth Connection

Operation

Ensure that the active sections of all the heating
elements are fully immersed in the fluid to be
heated at all times whilst energized.

Heat is transferred by means of electric heating
elements.

Control of the heater is facilitated by
thermostats, thermocouples or  RTDs and
reference should be made to the wiring diagram
inside cover to ensure that these are correctly
connected and set prior to energising the heater.

Where a manual reset thermostat or cut-out is
installed, the terminal box cover will have to be
removed after isolating the heater to enable a
reset to be carried out.

THESE HEATERS MUST BE EARTHED

An earth connection is provid-
ed inside the terminal box.

Routine Maintenance

Maintenance

All prevailing site safety regulations shall be
adhered to at all times.

Equipment is to be fully isolated  from the
electrical supply and locked off before and whilst
any work is being carried out.

3 Monthly

Generally inspect the equipment for external
damage or leaks.

6 Monthly

Isolate the electrical supply and remove the
cover.

Ensure the terminal box is clean and dry
internally.

Ensure the electrical terminals are intact and
secure.

Check that the heating element insulation
resistance is at least 2 mega ohms.

Check the continuity of all elements.

Refit cover with new gasket if required.

Ensure that earth continuity is maintained
between all exposed conductive material and
main site structure.

Annually

Carry out all 3 monthly and 6 monthly checks
as above.

Check for element failure or low insulation
resistance.

If heaters are being left unused for a period
greater than 3 months, carry out 6 monthly
maintenance before energizing.

Summary of Contents for CT plus 180

Page 1: ...sued By IJR Technical Dept Approved KS Dated May 2003 By Appointment to Her Majesty the Queen Boiler Manufacturers Engineers Hoval Ltd Newark Revision No 2 Issued By IJR Technical Dept Dated June 2006...

Page 2: ...derstood before attempting to install commission or operate this unit Introduction Description of CT plus Calorifier Technical and Performance Details CT plus Calorifier Installation and Piping Layout...

Page 3: ...ce with current I E E regulations relevant British Stan dard and Codes of Practice Building Regula tions and Local Authority Bylaws Commissioning should be arranged via the heating engineer Hoval engi...

Page 4: ...ss water gen eration the key requirement is for adequate quan tities of hot water over a relatively short period On this basis the CT plus will provide significantly higher flow rates than its continu...

Page 5: ...280 CT plus 420 CT plus 520 CT plus 180 CT plus 280 520 Water Content Weight Primarylitres Secondary litres Dry kg Wet kg 61 180 177 418 94 280 211 585 114 420 248 782 135 520 302 957 Working Pressure...

Page 6: ...load on the boiler for the calori er primary supply Note for Hydraulic Testing The primary jacket should not be pressurised without rst lling and sealing the inner stainless steel vessel An adjustabl...

Page 7: ...rom Main Headers Temperature control by diverting valve 3 7 Primary Water Secondary Water Installation and Piping Layouts Installation Position the calori ers as required ensuring that side and inspec...

Page 8: ...Secondary Systems Key 1 Relief valve adjacent to calori er 2 Spring loaded non return valve Note On CT plus 180 calori ers the secondary return and cold feed connections are at the top The cold feed s...

Page 9: ...aken to ensure they can pass the flow rates at the required pressure Hovals standard unvented system kits are sized to reduced incoming pressure to 3 bar at a flow rate that meets the peak output of t...

Page 10: ...rning On balanced systems with a common PRV Strainer and Double check valve ensure that the valves are sufficiently sized to cope with both hot and cold water demand Hoval Unvented System Kits Hoval h...

Page 11: ...ts Feeding two or more calorifiers Cold Feed Two or more calorifiers can be installed with individual unvented system kits Where the expansion vessels have been sized to share the total system expansi...

Page 12: ...water supplies Unvented Systems Unvented System with balanced hot and cold water services Cold Feed The hot and cold water supplies can be balanced by utilizing the same strainer and PRV to control t...

Page 13: ...n out strainer on commissioning and annually Check Expansion relief valve setting annually by twisting the cap on top of the valve Checkexpansionvesselgaschargepressure isolate thevessel drainoffanywa...

Page 14: ...o oper ate between 30 deg C and 80 deg C and is usu ally set to 60 deg C Pre commissioning Important Always fill the second ary side of the calorifier before the primary Pressurising the pri mary when...

Page 15: ...hose to primary drain which should be in stalled in primary outlet and run the hose to a gulley Note The primary side of the calorifier MUST always be drained before the secondary The secondary MUST...

Page 16: ...overcurrentdevice The cables must enter the heater terminal box via asuitablecableglandtomaintaintheIPratingand be fitted by a qualified person Earth Connection Operation Ensure that the active secti...

Page 17: ...17 Immersion heater Electrical Diagrams Immersion heater wiring diagrams...

Page 18: ...ler part document 4 Vent primary system 5 Change pump speed or pump Symptom Possible Cause Action A Secondary water temperature not as setting on thermostat 1 Leakage in system 2 Pump faulty or inoper...

Page 19: ...19 Electrical Diagrams Wiring Diagrams for Open Vented Calorifiers...

Page 20: ...20 Electrical Diagrams...

Page 21: ...21 Notes...

Page 22: ...Conservation of Energy Protection of the Environment Hoval Limited Northgate Newark Notts NG24 1JN Telephone 01636 672711 Fax 01636 673532...

Reviews: