61
4 220 456 / 02
MAINTENANCE
15.
- Remove siphon.
- Rinse the siphon.
- Check siphon seals for damage and replace
if necessary.
- Install siphon.
Siphon seal
Fig. 55
16. If a neutralisation unit is present, maintain it accord-
ing to the manufacturer’s operating instructions:
NOTICE
Reduction in the neutralisation effect
The neutralising agent in the neutralisation
unit is subject to degradation. The pH-neu-
tralising effect diminishes over time.
• Replace the neutralisation agent in the
neutralisation unit at the interval specified
by the manufacturer or if the pH value of
the condensate is < 6.5 after passing
through the neutralisation unit.
- While the heat generator is disconnected from the
electricity supply (blocking switch set to “0” heat
generator disconnected from the mains (e.g. main
switch, fuses)):
- Clean and check the neutralisation unit according
to the manufacturer’s instructions.
- If the pH value of the condensate is < 6.5, renew
the neutralisation agent according to the manu-
facturer’s instruction.
17. Cleaning and checking the condensate drain:
- Flush the condensate lines.
- Reassemble condensate drain and attach to
the siphon.
When installing the siphon and condensate
drain, the project engineering guidelines for
condensate drains must be complied with,
18. Fill the siphon (Fig. 55) and neutralisation unit, if pres-
ent, with water through the cleaning opening.
19.
Check the seal of the cleaning opening (Fig. 54) for
wear and replace if necessary.
!
WARNING
If the cleaning opening has a leak, flue gas
can escape and there is a risk of poisoning.
• Check the seal of the cleaning opening for
wear and tightness at the cover.
• Always close the cleaning opening.
20. Install the cover of the cleaning opening (Fig. 54) and
check it is gas-tight.
21. Closing the combustion chamber:
- Swivel the burner with boiler door closed down-
wards.
- Screw on the boiler door with star shaped knobs
22.
Cleaning the gas filter HFVR050, if present:
[K]
[H]
Die Dichtheit der Verschraubungen
ist mittels Leckspray zu prüfen
Beim Eindichten aller Gasamaturen darf mit dem
Auftragen des Dichtungsmaterials frühstens beim
zweiten Gewindegang begonnen werden
UltraGas (575-720)
Aktiengesellschaft
Aenderungen
Gezeich.
Geprueft
Massstab
Ersetzt durch:
Ersatz fuer:
Werkst.-code
Werkstoffnr.
Gegenstand
Werkstoff
Bemerkung
3
6 034 324K-3
Umbauset Gasventil V434
26.09.13
26.09.13
GASI
GASI
Art.Nr.
00
%
Umbauset Gasventil V434
Verwendet
in :
31-UltraGas (575-720)
Masse ohne Toleranzangabe
siehe Hovalnorm HN 020400
Pos.10 Faltkarton 655x305x266
Pos.11 Anl. Umbauset Gasventil VR434
Pos.12 Rücksendeformular - Gasventil
2
1
4
,5
(
)
5 3 5 , 8
1
1
6
(
)
Gas filter
Gas valve
Seal
Fig. 56
-
Remove the gas filter.
-
Clean the removed gas filter with clean running water.
-
Replace the gas filter if it is not possible to clean
it perfectly.
-
Dry the gas filter.
-
Reinstall the dry gas filter together with new seals.
23. Replace the seal on the gas connection and connect
the gas connection to gas valves.
4219076
27.05.2020
HOJK
ETL Brenner 50-UltraGas 2
(300-450)
A4
12976673 C84 000 02
/
/
/
Seal on gas connection
Fig. 57