MAINTENANCE
- Separate the condensate drain with siphon from the
condensate drain socket and ensure that the cleaning
water is directed into a collection tank or, if local regula-
tions permit, into the sewer system.
-
Thoroughly flush the heating surfaces (combustion
chamber and TurboFer
®
stainless steel composite
pipes (aluminium and stainless steel)) with a concen-
trated jet of water (e.g. using a spray gun attached to a
water hose).
-
If a higher cleaning effect is required:
Wet the heating surfaces with solvent-free cleans-
ing agent (e.g. soapy water), allow to act for a few
minutes and rinse with water.
- If deposits on the heating surfaces occur despite of an-
nual cleaning according to the steps above:
- Spray the heating surfaces with chloride-free, phos-
phoric cleansing agent (e.g. Desoxin) (Fig. 53), al-
low to act and flush with a jet of water of a high-pres
-
sure cleaner.
Spray bottle
Fig. 53
- The process can be repeated.
NOTICE
Cleansing agents in the condensate drain
and/or sewage system.
• Also rinse the condensate drain (tray and
siphon) after the cleaning procedure.
• Always observe the disposal instructions
of the cleansing agents (do not discharge
them into the sewage system).
13. Remove the cover from the cleaning opening.
Cleaning opening cover
Cleaning opening seal
Fig. 54
14. Clean condensate drip tray.
NOTICE
Flue gas accumulation in the heat generator
If the condensate cannot drain off, it will ac
-
cumulate in the boiler / flue gas collector. The
flue gas can no longer be transported away
without any obstruction.
• Always route the condensate drain with a
downwards slope in such a way that the
condensate is always guaranteed to flow
out without any obstruction.
• Check and clean the siphon, neutralisation
unit (if present) and condensate drain at
least 1x a year.
!
WARNING
Flue gas outlet
If there is no water in the siphon, or too little
water, then flue gas can escape through the
condensate drain. The concentration of flue
gas in the air can represent a fatal hazard.
•
Before recommissioning, fill the siphon
and, if present, the neutralisation unit with
water.
The water can be filled into the neutralisa
-
tion unit and the siphon via the cleaning