4.3
Chimney dimensions (overpressure)
Principles
• Height above sea level max. 1000 m
The first two metres of the flue pipe must ha ve the same
dimension as the flue gas out let.
• Combustion air:
- In the case of room air-independent operation (ac-
cessories optional) the air pipe must be at least the
same dimension as the flue gas pipe.
-
If the flue gas line diameter is greater than that of the
combustion air line, an individual calculation must be
made.
• Flue gas overpressure set:
- Compellingly necessary, included in the scope of de-
livery!
Boiler
Flue gas line (smooth walled)
Number of bow 90° (flue gas + air supply)
Type
Flue gas dim.
Dimension
Total pipe length in m (flue gas + air supply)
UltraGas
®
internal
DN
1
2
3
4
5 *
(250D)
254
200
50
50
48
45
(300D)
254
35
33
30
27
(250D)
254
250
50
50
50
50
(300D)
254
50
50
50
50
(400D)
306
50
50
50
50
(500D)
306
38
35
32
29
(400D)
306
300
50
50
50
50
(500D)
306
50
50
50
50
(600D)
306
50
50
50
50
(700D)
356
50
50
50
50
(800D)
356
45
40
35
31
(900D)
356
32
27
22
17
(1000D)
356
26
21
15
12
(700D)
356
350
50
50
50
50
(800D)
356
50
50
50
50
(900D)
356
50
50
50
50
(1000D)
356
50
50
50
42
(1150D)
356
35
25
14
–
(1300D)
356
17
6
–
–
(1150D)
356
400
50
50
50
50
(1300D)
356
50
50
50
50
(1440D)
356
50
50
50
42
(1700D)
500
500
50
50
50
50
(2000D)
500
500
50
50
50
50
Notice: The data contained in the table “Dimensions flue gas systems” represent guide values.
An exact calculation for the flue gas duct must be made on site.
* With 5 bends or more the feed pressure total at the combustion air/flue gas pipe is to be reduced by 30% for the calculation.
4.4
Flue gas line dimensions
(negative pressure)
The flue gas system is to be dimensioned in such a way
that no back circulation is possible in the room. A safe
operation of the flue gas system has to be proved by ap
-
proved measuring principles.
14
4 212 305 / 00
INSTALLATION