INSTALLATION

4. 

Installation

4.1 

Room air-dependent Installation

No binding values for the size of the intake air apertures 

are quoted in most relevant regulations. The sole require-

ment is that no vacuum occurs in the boiler room in ex-

cess of 3 N/mm

2

.

4.2 

Room air-independent Installation

The UltraGas

®

 twin boilers are fitted with intake flaps. An 

intake system can be mounted directly on these intake 

flaps at the installation site. (Remove blanking cover on 

the rear wall).

The combustion air intake can be executed either as a 

separate or common intake line.

The total pressure losses for the intake 

and flue gas lines is not to exceed 60 Pa.

If intake and flue gas lines are executed in the same di

-

mension, the effective pipeline length can be added and 

configured according to the UltraGas

®

 twin boiler project 

planning.

If the intake line is executed in a dimension different to 

that of the flue gas line, an individual calculation must be 

made by the chimney builder.

Summary of Contents for 30-UltraGas (1700D)

Page 1: ...up to 90 C1 in ac cordance with EN 483 and EN 677 They are designed for continuously adjustable reduced output operation in heating systems 1 see section technical data UltraGas 250D 2000D Condensing...

Page 2: ...om air independent Installation 11 4 3 Flue gas line dimensions overpressure 12 4 4 Flue gas line dimensions negative pressure 12 4 5 Hydraulic connection 13 4 6 Boiler sequential switching circuit El...

Page 3: ...expected reaction to your action i Note Provides important information Safety information Indicates an immediate hazard to persons Warning information Indicates danger to machines and Installa tions...

Page 4: ...25 PN6 8S 2a Return pipe connection option 1 DN80 PN6 4S DN80 PN6 4S DN125 PN6 8S DN125 PN6 8S DN150 PN6 8S DN150 PN6 8S 3 Gas connection Rp 1 Rp 1 Rp 1 Rp 2 Rp 2 Rp 2 4 Safety flow and flow calorifie...

Page 5: ...height is too small Reduction of measures possible See A minimal 2 Attention With A the burner is no longer swing out completely Cleaning makes more difficult 3 Feet can be shortened no base cladding...

Page 6: ...ltraGas Type A 250D 300D 1711 1771 400D 600D 1811 1871 700D 1000D 1958 2018 1150D 1440D 1984 2044 1700D 2000D 2037 2097 1 Neutralisation box 2 Condensate pump 3 Masonry base 4 Feet adjustable up to 20...

Page 7: ...80 18 80 18 80 18 80 Propane gas mbar 37 57 37 57 37 57 37 57 37 57 37 57 Gas connection value at 0 C 1013 mbar Natural gas E Wo 15 0 kWh m3 Hu 9 97 kWh m3 m3 h 23 1 28 2 37 6 47 0 56 6 65 2 Natural...

Page 8: ...18 80 18 80 Propane gas mbar 37 57 37 57 37 57 37 57 37 57 Gas connection value at 0 C 1013 mbar Natural gas E Wo 15 0 kWh m3 Hu 9 97 kWh m3 m3 h 75 4 84 9 94 3 108 5 122 7 Natural gas LL Wo 12 4 kWh...

Page 9: ...ar Natural gas E Wo 15 0 kWh m3 Hu 9 97 kWh m3 m3 h 135 5 160 5 188 6 Natural gas LL Wo 12 4 kWh m3 Hu 8 57 kWh m3 m3 h 158 0 187 2 220 0 Propane gas Hu 32 7 kWh m3 m3 h 52 3 Operation voltage V Hz 23...

Page 10: ...110 120 0 10 20 30 40 50 m3 h mbar UltraGas 700D 1000D 0 10 20 30 40 50 60 0 10 20 30 40 50 60 70 80 9 Volumenstrom m3 h Druckverlust mbar 0 m3 h mbar 0 20 40 60 80 100 0 20 40 60 80 100 120 140 Ultra...

Page 11: ...d directly on these intake flaps at the installation site Remove blanking cover on the rear wall The combustion air intake can be executed either as a separate or common intake line The total pressure...

Page 12: ...uide values An exact calculation for the flue gas duct must be made on site With 5 bends or more the residual overpressure of the device is to be reduced by 30 for the calculation 4 3 Flue gas line di...

Page 13: ...t the connection socket is located on the same size see chapter 3 1 4 6 Boiler sequential switching circuit Electri cal connections Parameters 4 6 1 Schematic coordination System Gas calorific value V...

Page 14: ...hkeit ein neues Shape zu nehmen hovhovalh hovalhova alhovalho Y10 2 Y10 1 UltraGas UltraGas Dies ist ein unerlaubter Weg Gehen Sie einen Schritt zur ck oder l schen Sie dieses Shape Sie haben die M gl...

Page 15: ...is is just a schematic For installation please use the detail plan Attenzione Per la messa in opera utilizzare le schema dettagliato Attention Pour la r alisation pratique de l installation il faut ut...

Page 16: ...For installation please use the detail plan Attenzione Per la messa in opera utilizzare le schema dettagliato Attention Pour la r alisation pratique de l installation il faut utiliser le sch ma d tail...

Page 17: ...400V supply required from UltraGas 1000 L PE N Netz L N 230V 10AT Netz Power supply Rete Secteur 0 1 SH 3 x 400V 10AT Netz Power supply Rete Secteur L1 L1 L2 L3 PE N N L2 L3 Version E 2 Verbindungshi...

Page 18: ...T Par 12 50 70 C WARMWASSER DHW ACQUA SANIT ECS Par 09 10K Version E 3 Verbindungshinweise Notice Nota Remarque Datei KBA020_V2 8 vsd Datum Name 21 01 10 Achtung F r die Installation muss das anlagenb...

Page 19: ...e Per la messa in opera utilizzare le schema dettagliato Attention Pour la r alisation pratique de l installation il faut utiliser le sch ma d taill Leg LK010 5 TopTronic T TopTronic T P P 0 10V Modul...

Page 20: ...A030_V2 8 vsd Datum Name 21 01 10 Achtung F r die Installation muss das anlagenbezogene Schema verwendet werden 2 8 KBA030_V2 8 V SD Attention This is just a schematic For installation please use the...

Page 21: ...imentation de 400V n cessaire partir de l UltraGas 1000 400V di alimentazione richiesti a partire dall UltraGas 1000 400V supply required from UltraGas 1000 L PE N Netz L N 230V 10AT Netz Power supply...

Page 22: ...Leg LK010 U TopTronic T 2 1 VE2 2 1 VE3 YK3 PE N YK1 PE N MK3 M 1 MK1 M 1 SLP M 1 N PE 2 L PE N MK 2 N PE 1 L PE N MK 1 L PE N DKP L PE N SLP L PE N VA1 L PE N VA2 RS T RFF T B A 1 2 SF 1 2 VF1 1 2 V...

Page 23: ...K2 PE N MK4 M 1 MK2 M 1 N PE 2 L PE N MK 2 N PE 1 L PE N MK 1 L PE N DKP L PE N SLP L PE N VA1 L PE N VA2 RS T RFF T B A 1 2 SF 1 2 VF1 1 2 VE1 A B T2B 1 2 VF2 1 2 KVLF 1 2 KSPF 1 2 IMP VF2 VF4 1 2 AF...

Page 24: ...re 1 BUS Verbindung zu Klemmen Kessel 1 2 BUS Connection to terminal block boiler 1 2 BUS Collegamento a morsettiera pompa di caldaia 1 2 BUS Connexion aux bornes de la chaudi re 1 2 B A T2B SVLF Mod...

Page 25: ...PE N VA2 1 2 SF 1 2 VF1 1 2 VE1 A B T2B 1 2 VF2 1 2 KVLF 1 2 KSPF 1 2 IMP 1 2 AF 1 2 KF 3 N 2 4 1 BZ SM N 5 11 12 13 14 15 16 U4 1 U4 3 U4 4 B2 T B5 B A RS485 3 2 1 4 5 6 X6 B11 N L Kessel 2 boiler 2...

Page 26: ...0K Par 01 05 Par 41 10min Par 04 80 C Par 44 00 Par 14 11min 1min FA Par 41 Par 26 00K FEUERUNGSAUT BOILER CONTR CONT BRUCIA ALLUM_AUTOM Par 03 20K Par 04 20K Par 41 10min Par 44 00 SUMMENVORL MAIN SU...

Page 27: ...tail plan Attenzione Per la messa in opera utilizzare le schema dettagliato Attention Pour la r alisation pratique de l installation il faut utiliser le sch ma d taill Leg LK010 TopTronic T TopTronic...

Page 28: ...N L1 L1 M5 1 M 1 N Startsequenz Start sequence Sequenza di avvio S quence de commencement 1 Absperrklappe auffahren Pumpe einschalten Open the shut off valve switch on the pump Apertura della valvola...

Page 29: ...ency M5 KKP pump directly by means of the shut off valve Wire the conventional pumps via the optional shut off valve limit switch pump starts up if open U TopTronic T 2 1 VE2 2 1 VE3 N PE 2 L PE N MK...

Page 30: ...l if several units please connect in line SH Main switch isolator outside of the boiler room SF Calorifier heater sensor SB R1 3 K System unit relay SB STW Relay kit flow switch SB GWP System unit gro...

Page 31: ...31 4 210 527 03...

Page 32: ...Conservation of Energy Protection of the Environment...

Reviews: