Circulator does not 

operate

Check aquastat setting

PROBLEM

CAUSE

SOLUTION

Boiler does not 

operate

Refer to boiler installation 

instructions

Check main service switch

Check fused disconnect

Peak use of hot water 

is greater than tank 

storage capacity

Determine peak usage, 

compare to tank capacity, 

and add additional storage 

(storage tank) if necessary

Improper aquastat 

setting

Turn tank aquastat to safe 

temperature setting

Electrical problem 

(relay, wiring, etc.)

Check fuse and replace

Check circuit breaker and 

reset (if applicable)

Check power supply

Aquastat set too low Raise aquastat setting to 

safe level.  See Section III

Undersized boiler with 

no priority to 

domestic hot water

Rewire for priority

No hot water at faucet

Water at faucet too 

hot

Aquastat set too high Lower aquastat setting to 

safe level

Tempering valve not 

properly set or 

defective

Check manufacturers 

instructions

Scale build-up

If boiler, circulator, and tank 

are operating satisfactorily, 

coil may have scale coating.

See Section VI for tank 

flushing procedure.

Check power supply

Replace as necessary

Faulty tank aquastat

Replace aquastat

Boiler cycles more 

than 5 times per day 

during hotest months

Excessive demand

Reduce demand or consider 

larger tank

Faulty aquastat

Replace aquastat

Boiler high limit set 

too low

Increase boiler high limit 

setting

Insufficient hot water

Rust staining; bad 

taste and odor in 

water

Iron/minerals in water 

supply

Filtration

Scale, hard white 

particles from faucets, 

popping sound from 

tank

Lime, water hardness 

above 7 grains-

120ppm

Water treatment; softener; 

etc.

Rotten egg odor

Hydrogen Sulfide

Flush tank with chlorine 

solution and install 

alumninum anode rod(s)

Air from hot water 

fixture

Electrolysis or air 

introduced by water 

supply

Properly ground heater & 

replace anode rod(s).  Check 

well pump system.

Reduction in recovery Dip tube broken or 

compromised by high 

chlorine in water

Replace dip tube

Inlet/Outlet fitting 

corrosion

Galvanic corrosion of 

dissimilar metals

Install dielectric unions

T&P gushing water 

Excessive water temp. 

(above 210 °F)

Adjust or replace aquastat 

and T&P valve

T&P Valve dripping 

water

Excessive water 

pressure (above 150 

psi)

Check incoming water 

supply pressure; closed loop 

system (System Plus) 

requires expansion tank

SECTION VI: TROUBLESHOOTING

Summary of Contents for HL119SK

Page 1: ...that commonly reduces the life of other in direct water heaters 3 Steel coil increases heat transfer for faster recov ery and the luxury of never running out of hot water 3 Coils and tank lining are...

Page 2: ...rvice This unit must be installed by licensed or authorized installers or technical personnel that service water heating equipment The heater must be installed in accordance with all local codes and o...

Page 3: ...Section I Specifications 4 Section II General Information 6 Section III Pre Installation 8 Section IV Installation 10 Section V Maintenance 13 Section VI Troubleshooting 14 Section VII Parts List 15...

Page 4: ...etting for normal residential use is 120 F ECR recommends a tempering valve or anti scald valve be installed and used according to the manufacturer s directions to prevent scalding HL30SK 22 35 3 4 27...

Page 5: ...78 88 000 190 96 000 202 104 000 214 111 000 HL80SK 188 76 000 212 91 000 224 98 000 221 97 000 233 104 000 245 112 000 257 119 000 HL119SK 220 76 000 244 91 000 256 98 000 253 97 000 265 104 000 277...

Page 6: ...provides limited control for domestic hot water temperature The proper temperature setting for domestic hot water use is 120 F 49 C If hotter water is required a tempering device or anti scald device...

Page 7: ...r system When hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at...

Page 8: ...th 180 F and 200 F boiler water To determine the appropriate circulator for your system follow these three steps 1 Calculate the pressure drop of all straight pipe and fittings on the supply and retur...

Page 9: ...inimum coil output assume coil output boiler output listed in Tables 2 and 3 is not met the output first hour rating of the water heater will not be met at the selected flow rate To approximate the re...

Page 10: ...be minimized A flow check valve must be installed on the return line All piping to the inlet cold and outlet hot domestic water connections should be new copper with a minimum size of 1 2 ID for model...

Page 11: ...IV INSTALLATION cont CHECK VALVES ZONE CIRCULATORS ISOLATION VALVES ADDITIONAL ZONES INDIRECT CIRCULATOR INDIRECT WATER HEATER TO HEATING ZONE AIR SEPARATOR AIR VENT EXPANSION TANK COLD WATER INLET BO...

Page 12: ...the indirect calls for heat the indirect coil tank heater circulator must start rather than opening a zone valve the system circulator stays off and the boiler must light to reach high limit WIRING NO...

Page 13: ...nd at least yearly once a time interval for inspection has been developed It is recommended to check the rod s six months after the heater is installed If the anode rod had reduced in size by two thir...

Page 14: ...k power supply Replace as necessary Faulty tank aquastat Replace aquastat Boiler cycles more than 5 times per day during hotest months Excessive demand Reduce demand or consider larger tank Faulty aqu...

Page 15: ...HL50SK 3 HL80SK 3 HL119SK 5 Leak Detector Fitting HL30SK HL40SK 5 Leak Detector Fitting HL50SK HL80SK HL119SK 6 ST00601 1 T P Relief Valve 3 4 LL100XL HL30SK HL40SK HL50SK 6 ST01001 1 T P Relief Valve...

Page 16: ...e unauthorized alteration improper repair or maintenance excessive pressure or leaks at water connections or any other similar cause 5 The failure or malfunction results from failure to keep the unit...

Reviews: