Note: The start circuit of the compressor is timed such that at power-up and during
any compressor off time, there will be at least a 1/ minute delay before the
compressor will start. The only exception is when the overload activates and
deactivates. The compressor has a 1/ minute minimum run time during every
run cycle.
2. Freezer (except freezer side of RFH1-SSB-HD) auxiliary code P5 and earlier
a) Sequence of Operation
Cycle On
(Cut-on
temperature reached)
[Minimum .5 minutes]
1. Compressor on
. Condenser on
3. Evaporator on
2.5 minute delay
1. Compressor start-up
. Condenser fan start-up
3. Evaporator fan start-up
POWER ON
Board Self Check
Display reads "r_##"
(## is board revision)
Frame heaters on
Cycle Off
(Cut-out
temperature reached)
[Minimum .5 minutes]
1. Compressor off
. Condenser fan off
3. Evaporator fan off
Defrost Start
Preprogrammed time interval
1. Compressor off
. Evaporator fan off
3. Condenser fan off
4. Defrost heater on
5. "dEF" displayed
Defrost End
Defrost thermistor
reaches 100°F;
Defrost heater off
Five minutes after
defrost heater off
1. Compressor on
. Condenser fan on
Evaporator temperature
reaches below 70°F
1. Evaporator fan on
Cabinet temperature reads
a value below 15°F above
the setpoint.
"dEF" no longer displayed,
cabinet temp. displayed.
Normal cycling continues
Summary of Contents for TempGuard FH1-SSB
Page 7: ... 2 RH1 SSB HD FH1 SSB HD RFH1 SSB HD RH1 SSB GD mm in ...
Page 8: ... 3 RH2 SSB HD FH2 SSB HD RFH2 SSB HD RH2 SSB GD mm in ...
Page 9: ... 4 RH3 SSB HD FH3 SSB HD RFH3 SSB HD RH3 SSB GD mm in ...
Page 10: ...10 5 PTR1SSB xxxx PTR1 SSB01 10 mm in ...
Page 12: ...12 b Timing Chart For refrigerator and refrigerator side of Dual Temp models ...
Page 16: ...16 b Timing Chart For freezer except freezer side of RFH1 SSB HD auxiliary code P6 and later ...
Page 18: ...18 b Timing Chart For freezer side of RFH1 SSB HD ...