34
F. Diagnostic Charts
Before consulting the diagnostic charts, check for correct installation, proper voltage per unit
nameplate, and adequate water supply. Check CB using the steps in "IV.B. Control Board
Check." Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10, and
S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, 6 are
cleaning adjustments and the settings are flexible. For factory default settings, see "II.C.3.a)
Default Dip Switch Settings."
1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply
a) Off, blown fuse, or tripped breaker.
b) Not within specifications.
2. Water Supply
a) Water supply off or improper water pressure.
b) External water filters clogged.
3. Fuse (SRK Control Box)
a) Blown.
4. High-Pressure Switch (SRK)
a) Dirty condenser.
b) Condensing unit fan not operating.
c) Headmaster (C.P.R.) open.
d) Refrigerant overcharged.
e) Bad contacts.
f) Refrigerant lines or components plugged.
5. Thermostat (SRK)
a) Ambient temperature too warm.
b) Compressor or compressor components faulty.
c) Defective.
d) Hot gas valve open.
e) Dirty condenser.
f) Condensing unit fan not operating.
6. Wire Harness
a) Disconnected or loose connection.
7. Fuse (KMS Switch Box)
a) Blown.
8. Control Switch
a) In "WASH" or "OFF" position.
b) Bad contacts.
9. Control Transformer
(115V/10.5V)
a) Coil winding open or shorted.
10. Interlock Switch (Cleaning Valve) a) In open (vertical) position.
b) Bad contacts.
11. Control Board
See "IV.B. Control Board Check"
a) In alarm.
b) BC OPEN, yellow LED on (bin full).
c) Defective.
12. Bin Control
See "IV.C. Bin Control Check and
Cleaning"
a) Tripped with bin filled with ice.
b) Actuator does not move freely.
c) Defective.
13. Inlet Water Valve
a) Screen or orifice clogged.
b) Coil winding open.
c) Open in freeze cycle.