4) Remove the hexagon head bolts with washers securing the condenser fan motor
bracket to the base, and remove the condenser fan motor assembly.
5) Remove the screw securing the unit side panel, and take off the side panel.
6) Remove the terminal cover enclosing the compressor electrical parts.
7) Remove the overload relay and start relay.
8) Disconnect the discharge and suction pipes using brazing equipment.
9) Remove the bolts securing the compressor.
10) To replace the removed parts, reverse the above removal procedure.
Note: 1. To recharge the refrigerant, install a stop valve in the access line.
2. Evacuation time must be at least 1 hour.
3. To prevent oxidation, braze the pipes with nitrogen gas flowing.
4. Check for gas leaks, remove flux and oxide film, and apply anti-corrosion
treatment.
5. While brazing, use a wet towel to protect the plastic parts and electrical parts
from burner flame.
Shroud
(Condenser Cover)
Drier
Heat Exchanger
Compressor
Access Valve
Condenser
Refrigeration
Unit Base
Condenser Fan
Motor Assembly