26
Operations
1. Under temperature measuring and controlling status:
1) Press the set key for 3 seconds:
When the keypad password is set as “0”, the set indicator light comes on and the screen
displays the “F01” menu. There is no password authentication, so directly enter the
menu mode to set parameter.
When the keypad password is not set as “0”, the set indicator light flashes and the
screen displays “00”. Press the up or down key to input the password. Press the set key
to confirm the password input. Then, the system enters the menu setting status if the
password is correct. If the password is incorrect, the set indicator light goes off and the
system goes back to the normal measuring and controlling status.
2) Parameter check:
Press the up key. The set indicator light flashes and the screen displays the set point
temperature.
Press the down key. The set indicator light flashes and the screen displays the
temperature of the evaporator sensor.
2. After entering the menu setting status, press the up or down key to choose the desired
menu item (from F01 to F09).
3. After choosing the desired menu item, press the set key to set parameter value. Press
the up or down key to adjust parameter value, and then repress the set key to go back
to the menu setting status.
4. Under the setting status, press the defrost/reset key or perform no operation for 30
seconds. The system will save the parameters and exit from the parameter setting
mode.
5. Press the defrost/reset key for 3 seconds to start or stop the manual defrost cycle.
Output Control
1. Compressor:
The compressor starts up when the delay time runs out, if the measured temperature is
higher than the “fixed temperature value + temperature return difference”.
The compressor stops running when the measured temperature is lower than the set point
temperature.
2. Defrosting:
Defrosting starts automatically according to the defrost cycle setting, or can be started
manually. If the evaporator sensor is activated and the evaporator sensor temperature is
higher than the defrost termination temperature, the manual start is not available.
Summary of Contents for FTC-120MDA
Page 6: ...3 2 DIMENSIONS SPECIFICATIONS a RTC 120MNA ...
Page 7: ...4 b RTC 120MDA ...
Page 8: ...5 c RTC 150MNA ...
Page 9: ...6 d RTC 150MDA ...
Page 10: ...7 e RTC 180MNA ...
Page 11: ...8 f RTC 180MDA ...
Page 12: ...9 g FTC 120MNA ...
Page 13: ...10 h FTC 120MDA ...
Page 14: ...11 i FTC 150MNA ...
Page 15: ...12 j FTC 150MDA ...
Page 16: ...13 k FTC 180MNA ...
Page 17: ...14 l FTC 180MDA ...
Page 18: ...15 II TECHNICAL INFORMATION 1 WIRING DIAGRAM a RTC SERIES ...
Page 19: ...16 b FTC 120MNA FTC 120MDA FTC 150MNA ...