12
- compressor activity will depend on C4 and C5 parameters
- the defrost will not be activated
Pr2
Evaporator/defrost probe error
Solutions:
- the same as in the previous example, but with regard to the evaporator probe or the condenser probe
Main consequences:
- if P4 parameter is set at 1, the defrost interval will last for the amount of time set with d3 parameter
- if P4 parameter is set at 1 and d8 parameter is set at 2 or to 3, the device will operate as if d8 parameter were set at 0
-
if P4 parameter is set at 2, the condenser overheated alarm (code “
COH
”) will never be activated
- if P4 parameter is set at 2, the compressor shut down alarm (
code “
CSd
”) will never be activated
When the cause of the error disappears, the device restores normal operation.
DEFROSTING
THE DEFROSTING OF THE REFRIGERATING CABINETS IS TOTALLY AUTOMATIC.
The air defrosting operation of the appliances occurs automatically every 6 hours.
The defrosting lasts 20 minutes.
A defrost cycle can be selected at any time by pressing button “
”; for 5 seconds. The next automatic
defrost cycle will start 6 hours after pressing the button.
LOADING THE PRODUCT
•
Distribute the product evenly inside the appliance
compartments so as to allow adequate air circulation;
•
Do not obstruct the ventilation areas of the cooling
system located on the left of the compartment;
•
Do not use the lower drawer on the right to store
foodstuffs requiring low-temperature storing;
•
Cover or wrap foodstuffs with specific protective films
before storing;
•
Do not introduce hot foodstuffs or beverages;
•
Do not leave the door open longer than is necessary
when introducing or removing products;
•
Only load the top shelf up to the stacking mark;
•
Do not place products below the bottom shelf support.
•
Only load lower drawers up to the stacking mark.
STOPPING
In any condition and for stopping the machine it is enough to press the main switch 1 in OFF position; the
pilot light of the switch will go out.
WARNING
: the main switch 1 DOES NOT insulate the machine from the electric
current.
Set the general cut-out in OFF position.
1