background image

 

 

MAN0965-03-EN 

 

 

  Specifications/Installation 

 

10/15/2013                          

No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, LLC. Information in this document is subject to change without notice.

 

 

Page 

1

 of 

6

 

 

 

SmartBlock I/O Module - HE579DAC107/HE579DAC207 

8/4 Channel Current and Voltage Output 

0-5V / 0-10V / 4-20mA / 0-20mA - CsCAN 

 

1.  SPECIFICATIONS / DIMENSIONS 

ANALOG OUT 

Number of Outputs 

8 (207) or 4 (107) 

Isolation  
(Power to Analog Output) 

1000V DC 

IEC61010-1 300V RMS 

Output Ranges 

0-5V, 0-10V DC 

4-20mA, 0-20mA DC 

Isolation Method 

Magnetic 

Resolution 

14 bits 

Output Clamp  

-.5/+24V, 600Wpk 

Accuracy, 25°C 

0.1% 

Output Type 

Sourcing 

Load Resistance 

V: 500 ohms Min 

mA: 500 ohms Max 

Register Value for  
Nominal Full Scale 

32000 

GENERAL SPECIFICATIONS 

Required Power @ 24 VDC 

(Voltage Mode 2KΩ)

 

(207) 145mA 
(107) 105mA 

Cooling Method 

Self-cooling 

Relative Humidity 

5 to 95% Non-condensing 

Required Power @ 24 VDC 

(Voltage Mode 2KΩ)

 

(207) 255mA 
(107) 190mA 

Altitude for use 

Up to 2,000m 

Pollution Degree 

2 or lower 

Voltage Input 

10-30 VDS 

Weight 

12oz/340g 

Operating Temperature 

0

 to 60

Atmosphere 

Free from corrosive gases 

and excessive dust 

Storage Temperature 

-25

 to 70

DIMENSIONS 

Width 

4.48” 

(113.7mm) 

Length 

4.56” 

(115.8mm) 

Height 

2.16” (54.8mm) 

Height w/ connector 

2.84” (72.1mm) 

 

 

 

 

 

 

 

 

 

 

 

 

2.  TECHNICAL SUPPORT 

North America: 

 

Tel:  317 916-4274 

    Fax: 317 639-4279 

Web

http://www.heapg.com

   

Email

[email protected]

 

Europe: 

 

Tel:  +353-21-4321266    Fax: +353-21-4321826        Web

http://www.horner-apg.com

 

Email

[email protected]

 

 
 

 

 

Status LEDs 

J2 Outputs 5 -8 

J1 Outputs 1-4 

Network ID 
Selector Switches 

CAN and  

power connector 

Earth Ground Location 

Summary of Contents for SmartBlock HE579DAC107

Page 1: ...er Value for Nominal Full Scale 32000 GENERAL SPECIFICATIONS Required Power 24 VDC Voltage Mode 2KΩ 207 145mA 107 105mA Cooling Method Self cooling Relative Humidity 5 to 95 Non condensing Required Power 24 VDC Voltage Mode 2KΩ 207 255mA 107 190mA Altitude for use Up to 2 000m Pollution Degree 2 or lower Voltage Input 10 30 VDS Weight 12oz 340g Operating Temperature 0 to 60 C Atmosphere Free from ...

Page 2: ...ns Installation 10 15 2013 No part of this publication may be reproduced without the prior agreement and written permission of Horner APG LLC Information in this document is subject to change without notice Page 2 of 6 3 WIRING ...

Page 3: ...ck I O For advanced operations such as on the fly changes to the output type please see the following chapter on network data and the SmartStix and SmartBlock programming guide To configure SmartBlock I O from Cscape open the Hardware Configuration dialog from the Controller Hardware Configuration menu 1 Select the option for CsCAN I O 2 Click Add 3 Select the SmartStix Tab and select the device t...

Page 4: ...ed applications you may use NetPut functions to write this data Please see the advanced programming guide MAN0880 for more details Word Description 1 8 Analog Data Data for analog output channels 1 to 8 9 16 Default Data Analog output default state on error or stop if selected Produced Digital Data This data is sent from the SmartBlock to the controller Normally this data is mapped into specific r...

Page 5: ... 157 9 D 185 B 9 213 D 5 241 F 1 17 1 1 45 2 D 74 4 A 102 6 6 130 8 2 158 9 E 186 B A 214 D 6 242 F 2 18 1 2 46 2 E 75 4 B 103 6 7 131 8 3 159 9 F 187 B B 215 D 7 243 F 3 19 1 3 47 2 F 76 4 C 104 6 8 132 8 4 160 A 0 188 B C 216 D 8 244 F 4 20 1 4 48 3 0 77 4 D 105 6 9 133 8 5 161 A 1 189 B D 217 D 9 245 F 5 21 1 5 49 3 1 78 4 E 106 6 A 134 8 6 162 A 2 190 B E 218 D A 246 F 6 22 1 6 50 3 2 79 4 F 1...

Page 6: ...uracy will be affected Any thermocouple should be grounded in one place at most When found on the product the following symbols specify All applicable codes and standards need to be followed in the installation of this product For I O wiring discrete use the following wire type or equivalent Belden 9918 18 AWG or larger Adhere to the following safety precautions whenever any type of connection is ...

Reviews: