MAN0964-14-EN_XL4_XL4P_UM
N o v e m b e r 1 0 , 2 0 2 1
P a g e 119 | 194
Table 12.3 - Ethernet Status Word Register Format
High Byte
Low Byte
Bit
16
Bit
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit 1
0
0
Dup
Spd
0
Rx
Tx
Link
TCP Connections
Status Bit(s)
Status Indication
Status Values
Minimum
Maximum
0
Reserved
Always 0
Dup
Link Duplex (Auto-Negotiated)
0 = Half Duplex
1 = Full Duplex
Spd
Link Speed (Auto-Negotiated)
0 = 10MHz
1 = 100MHz
Rx
Receive State
0 = Inactive
1 = Active
Tx
Transmit State
0 = Inactive
1 = Active
Link
Link State
0 = Down
1 = Up
TCP Connections
Total Number of Active TCP Connections
(CsCAN, SRTP, Modbus, EIP, FTP, HTTP)
0
40
Version Register: Enter an OCS Register reference (such as %R101) to indicate which 16-bit OCS
register will have the Ethernet Firmware Version written to it. The value stored in the Version
Register is (Ethernet Firmware Version * 100). For example, for Ethernet Firmware Version
4.30, the Version register will contain 430.
Get Setting From:
“Get settings from” allows the programmer to either configure the IP Address, Net Mask, or
Gateway for two functions: Configuration or Register.
Configuration
—
The configuration for the IP Address, Net Mask, or the Gateway will be assigned
using the value in the Default Settings in this window.
Register
—
The configuration for the IP Address, Net Mask, or the Gateway will be assigned using
the values in the registers assigned.
NOTE
: The low octet of the IP Address can be replaced with the unit’s CAN Network ID, by
checking the Use CAN ID for last Octet checkbox.