27
9
Faults
9.1 Information
Code
Name
Description
Consequence/action
CGH_I001
ManualStop
STOP button actuated during
charging
Charge interruptions result in defective charging and without electrolyte
circulation to battery damage. Wait until charging has ended and Complete
is illuminated.
CGH_I002
PilotStop
Contact lost during charging
in pilot function
Charge interruptions result in defective charging and without electrolyte
circulation to battery damage. Wait until charging has ended and Complete
is illuminated.
9.2 Warnings
Code
Name
Description
Consequence/action
CHG_W001
TemperaturePowerModule
Temperature issue in the
power module
Overheating of the charger and loss of charge current. Please review the
ventilation and ambient temperature with respect to proper use.
CHG_W002
ComWarningPowerModule
Power module
communication fault
Device may stop charging. Please notify the HOPPECKE service technician.
CHG_W003
ComWarningStatusBoard
Status board
communication fault
Device may stop charging. Please notify the HOPPECKE service technician.
CHG_W004
SDCardAlmostFull
The SD card is 99 % full
Device may stop charging. Please notify the HOPPECKE service technician.
CHG_W007
HardwarePowerModule-
Warning
Power module
hardware fault
N/A
CHG_W008
MissingSDCard
No memory card available
Defective memory card, charging continues as normal.
Although data will no longer be recorded.
CHG_W009
PowerLoss
Loss of mains power
One phase of the AC voltage supply is absent in the case of three-phase
devices. Please have an electrician inspect the mains supply.
CHG_W010
TemperatureBattery
Battery interface reports:
Battery very hot (> 55 °C)
The connected battery is no longer being used correctly and will wear out
and fail prematurely.
Please use a replacement battery.
CHG_W011
ElectrolyteWarning
Battery interface reports:
Low electrolyte level at start
of charging
The electrolyte level in the connected battery is too low and will lead to
direct, irreversible capacity loss.
Please fill with demineralised water.
CHG_W012
PlugWearWarning
Warning of plug wear
The configured threshold has been exceeded.
Replace plug and reset counter.
CHG_W013
TrakAirPressureHighWarning Pressure too high
trak | air is deactivated. Check the pump.
CHG_W014
TrakAirPressureLowWarning Pressure too low
trak | air is deactivated. Check the pump.
CHG_W015
TrakAirLeakageHighWarning After deactivating trak | air the
pressure alteration per time
is too high
Wait for 60 seconds. Check the pump.
CHG_W016
ComTrakCom
Values outside of tolerance
Restart the system.
CHG_W018
Service interval will soon
expire
Please notify the HOPPECKE service technician.
Should there be a problem with your charger, you can find information
about the cause and possible remedial actions here.
Please have the following information ready if you would like to report
a fault (it can be found on the device's type plate):
Type designation and serial number of the affected charger
Please also note the following before making contact:
What is being shown on the display? Is there a warning or fault
signal? Have you already read the error text?
When did you notice the error message?
When was the charger commissioned?
Where is the charger being used?
Who is the contact person in your company?
Summary of Contents for trak HF premium
Page 186: ...186 Notizen Notes...
Page 187: ...187 Notizen Notes...