Hoppecke 5 OPzV 250 Installation, Commissioning And Operating Instructions Download Page 12

22

23

Installation, commissioning and operating instructions for valve-regulated stationary lead-acid batteries
7140203153 V1.4 (09.2018)

Installation, commissioning and operating instructions for valve-regulated stationary lead-acid batteries

7140203153 V1.4 (09.2018)

5.1.1 Calculation of safety distance

In close proximity of the batteries the dilution of explosive gases is not always given. Therefore a safety distance 
has to be realized by a clearance, in which there must not be any sparking or glowing equipments (max. surface 
temperature 300°C). The diffusion of the oxyhydrogen depends on the gas release and the ventilation close 
to the battery. For the following calculation of the safety distance ‘d’ it can be assumed that the oxyhydrogen 
expands spherical. Figure 5.1 depicts a graphic approximation of the safety distance ‘d’ depending on the 
battery capacity. Subsequently a detailed calculation is shown.

Safety clearance:

Required safety clearance needs to be calculated according to formula stated in IEC 62485-2.

Volumes of a hemisphere:

Air volume flow required to reduce the concentration of generated hydrogen H

2

 in the air to 4% max.:

Required radius of the hemisphere:

Fig. 5–1: Safety distance based on battery capacity (Source HOPPECKE)

Safety clearance d [mm]

Battery capacity C [Ah]

VLA battery float charge mode
VRLA battery float charge mode

VLA battery boost charge mode
VRLA battery boost charge mode

Requirement

Our recommendation

Ventilation source

Sufficient room ventilation is absolutely required to limit the  

hydrogen concentration (H2 concentration) in the ambient air of 

the battery room to a value of <2% by volume.

Hydrogen is lighter than air. Make sure that hydrogen does not 

accumulate (e.g., in the ceiling area). Ventilation and deaerati-

on openings should be placed near the ceiling. (see also 

Chap. 

5.2.1.1

 and 

Chap. 5.2.1.2

).

Environment

The ambience should be clean and dry. Water, oil and dirt must be kept away 

from the cell surface.

Passageway width  

in front of and between 

the battery racks  

(and cabinets)

Europe:                 Passageway  width  =  1.5  x  cell  width  (installation  depth),  at  least  

500 mm (see also IEC 62485-2). 

USA:  

36“ or. 915 mm

HOPPECKE recommendation:
If possible at the installation location: 1 m.
Otherwise:  in accordance with local regulations.

Minimum distances

Rack to wall
Battery to wall
Conductive parts to ground 

Battery end terminals
Battery to sources of ignition
Upper surface of battery to 
next tier of rack or bottom 
of the next cabinet

     50 mm
   100 mm
1.500 mm   for U

nom

 or U

part

 >120 V VDC between non-insulated and grounded 

parts (e.g. water lines)

1.500 mm  for U

nom

 >120 V DC

See calculation of the safety distance 

Chap. 5.1.1.

   250 mm   It mus be possible to measure the voltage.

Access door

Lockable and fire retardant (T90).

Lighting

Recommend: at least 100 lx.

Labeling

Warning signs in accordance with IEC 62485-2.

 

 

 Warning sign depicting risk of electrical volta-

ge only necessary if battery voltage exceeds 

60V DC.  

Risk of explosion

No sources with ignition (e.g. open flame, glowing objects, electrical switches, 

sparks) near to the cell openings.

Ambient temperature

The recommended operating temperature ist between 10 °C and 30 °C. The 

optimal temperature is 20 °C ± 5 K. Higher temperatures shorten the service 

life of the battery. All technical data is valid for the nominal temperature of 20 

° C. Lower temperatures decrease battery capacity. Exceeding the limit tempe-

ratures of 55 °C is not permissible. Avoid operating at temperatures en excess 

of 45 °C for long periods of time.

Batteries should not exposed to direct sunlight or near heat sources.

Ambient air

The air in the battery room must be free of impurities, e.g. suspended matter, 

metal particles or flammable gases.

The humidity should be at a maximum of 85%.

Earthing

If you ground the racks or battery cabinets, make sure that you use a connection 

to a reliable grounding point.

Battery installation

We recommend that batteries are properly installed in HOPPECKE battery racks 

or cabinets. The use of other operator-specific solutions may render the warran-

ty for the batteries null and void.

Country-specific  

regulations

Some countries require batteries and racks to be installed in collection tanks. 

Please observe all local regulations and contact you local HOPPECKE represen-

tative if necessary.

Tab. 5–1: Demands on the erection site

Danger!

Summary of Contents for 5 OPzV 250

Page 1: ...for valve regulated stationary lead acid batteries Installation commissioning and operating instructions Similar to the illustration...

Page 2: ...development For this reason there may be discrepancies between the product that you have purchased and the product as represented in this documentation Please keep this documentation so that it is im...

Page 3: ...ely from normal household wastes General notice or tip for better understanding and optimum use of the battery or batteries Pb 0 Safety notices 0 1 General Information Danger Incorrect use of the prod...

Page 4: ...ive counterparts of old and new names In the rest of this document old names will be listed in brackets Pb Following symbols and pictograms are pictured on each battery cell or on each battery block R...

Page 5: ...e for Maintenance Testing and Replacement of Valve Regulated Lead Acid VRLA Batteries for Stationary Applications IEEE Standard 1189 2007 Guide for Selection of Valve Regulated Lead Acid VRLA Batterie...

Page 6: ...ls blocks into the racks 30 5 10 Connecting the batteries 32 5 10 1 Connection terminals 32 5 10 2 Type of connection cable 32 5 10 3 Clamping batteries using battery connectors 32 5 10 4 Installing t...

Page 7: ...type 250 Nominal capacity C10 capacity during discharge with ten hours current I10 over a discharge time of 10 h t10 267 actual capacity C10 capacity of discharge with 10 h current 5 OPzV 250 2V 250A...

Page 8: ...ly However they contain diluted sulfuric acid H2 SO4 that is bonded in gel or glass mat The bonded sulfuric acid is extremely corrosive and can cause serious injury Further information to sulfuric aci...

Page 9: ...ic shock If a second accidental ground connection is made there is a risk of short circuit fire and explo sion If you have questions about these instructions or any other questions regarding safety wh...

Page 10: ...r is still present to make sure that your shipment is complete compare with the delivery note In particular check the number of battery pallets and the number of boxes with accessories Then inspect th...

Page 11: ...ention If the cells batteries are to be stored for a long period of time store them fully charged in a dry frost free location Avoid direct sunlight To prevent damage to the batteries an equalizing ch...

Page 12: ...cell width installation depth at least 500 mm see also IEC 62485 2 USA 36 or 915 mm HOPPECKE recommendation If possible at the installation location 1 m Otherwise in accordance with local regulations...

Page 13: ...always filled before delivery Sealed stationary lead acid battery cells must not be refilled with water during the entire battery service life Overpressure valves are used as sealing plugs These plugs...

Page 14: ...d ventilation for hydrogen generated by batteries Chap 10 Required ventilation for hydrogen generated by bat teries 5 3 Conducting an open circuit voltage measurement Before installing the batteries c...

Page 15: ...c tions mask bad cells and blocks and could cause individual battery strings to overload 2 Only batteries of the same type and same state of charge should be connected same battery type plate size and...

Page 16: ...e after another into the racks so that they are angled and level with the correct polarity Remove all transportation and hoisting equipment For large batteries it is required that you begin installati...

Page 17: ...rs must be furnished with additional insulation Avoid mechanical stress on the cell battery terminals Protect cables with large cross sections using cable ties and cable clamps The connection cables b...

Page 18: ...brations which could loosen the connection under certain cir cumstances The cables must be supported so that no mechanical load can be transferred to the connection terminals cable trays cable ducts c...

Page 19: ...n be omitted 6 1 Discharging Attention Never allow the final discharge voltage of the battery to drop below the voltage corresponding to the discharge current Unless the manufacturer has specified oth...

Page 20: ...ber of cells in series occurs after charging DC power supply Electrical Load Battery 6 2 2 Floating operation The following is characteristic for this operating mode Consumers direct current source an...

Page 21: ...on of the equalizing charge Perform the equalizing charge as follows 1 Charging with IU characteristic up to max voltage U 2 4 V cell up to 48 hours The charge current must not be higher than 20 A per...

Page 22: ...power VR L OPzV solar power OPzV bloc solar power and sun power VR M solar bloc batteries This chapter contains instructions for charging of HOPPECKE sun power VR L OPzV solar power OPzV bloc solar p...

Page 23: ...charge of 80 Fig 7 9 Endurance in cycles of sun power VR L OPzV solar power as a function of ambient temperature Cycle Number n Depth of Discharge DoD Cycles n Ambient Temperature in C 7 3 Temperature...

Page 24: ...depicts dependency of the endurance in cycles on depth of discharge and temperature Fig 7 10 Endurance in cycles of sun power VR L OPzV solar power depending on DoD and temperature 7 4 3 Electrolyte f...

Page 25: ...mum voltage is reached 11 Reconnect the battery system as originally connected and perform a boost charge see Chap 5 13 9 2 Performing the capacity test extended version Preparation The best and quick...

Page 26: ...ecting the correct discharge current or the correct discharge power Carry out the battery discharge in accordance with the regulations on performing capacity tests EN 60896 21 The discharge current an...

Page 27: ...ells The battery is on float charge at 2 25 V per cell CN Nominal capacity of the battery 200 Ah n Number of cells 2 x 30 cells fg Gas emissions factor 0 2 fs Safety factor 5 Ifloat 1 mA Ah Cell numer...

Page 28: ...w of 0 6 m3 h What factors must be considered when installing a natural ventilation system If possible the ventilation openings should be positioned on opposite walls If they must both be on the same...

Page 29: ...fire extinguishers are not suitable amongst others because of only minor efficiency possible risks or collateral damages Special protective equipment For larger stationary battery installations or lar...

Page 30: ...67 no transport as dangerous goods non spillable batteries are not subject to other requirements of IATA DGR if they meet the requirements of Special Provision A 67 Provided that poles are secured ag...

Page 31: ...correct or up to date Packing Instruction P 801 a transport as dangerous packing in accu Special Provision VV 14 transport as dangerous ADR Tunnel restriction code Note these references can be applie...

Page 32: ...on dispose with due regard to the official local regu lations 7 Handling and storage Store frost free under roof Seek agreement with local water authorities in case of larger quan tities Observe VAWS...

Page 33: ...l details in this brochure are based on state of the art technology Our products are subject to constant development We therefore reserve the right to make changes HOPPECKE Batterien GmbH Co KG P O Bo...

Reviews: