WV8840A WATER HEATER CONTROLS

69-2247—05

6

3.

After status indicator analysis and appliance repair 

is complete, turn device knob to OFF, wait until the 

indicator goes out, then perform lighting procedure.

4.

Status indicator light should be in normal mode

(1 flash) with the knob in the PILOT position. Turn 

the device knob past the water temperature in the 

tank should turn on the main burner. The Status 

indicator light will strobe every three seconds when 

there is a call for heat.

5.

In the event of multiple failure codes, the next failure 

code follows the previous failure code by 

approximately three seconds with higher flash count 

first.

*

LED Error Codes are flashed once per second, with a three-second pause between repeating the error code.

**

Maximum two different errors can be displayed simultaneously if more than one error has been detected.

Table 3. Troubleshooting with status light visual indication.

LED Error 

Code

**

Number of LED Flashes

*

Detected Failure

Recommended Action

Normal 

operation. 

No action 

required.

1 flash 

every 3 

seconds

Not an error; indicates 

the electronics is 

holding the Pilot Valve 

open and the Main 

Valve closed.

You can now turn the knob to a 

desired setpoint temperature. LED 

will continue to flash 1 time every 3 

seconds while in Idle mode (no call for 

heat).

Strobe 

every 3 

seconds

Not an error; indicates 

call for heat during 

normal operation, 

Main valve open.

None.

Action 

required.

2 flashes

Low thermopile 

voltage; main valve not 

turned ON.

Check thermopile and its 

connections. Check pilot flame.

4 flashes

Temperature cut-out 

limit reached.

Check the valves and the water 

temperature sensor. Reduce the 

water temperature setpoint. 

Thoroughly check out main valve 

operation and water temperature 

control before walking away.

5 flashes

Water temperature 

sensor failure.

Check water temperature sensor and 

its connection for open circuits, 

shorts, or differences in resistance 

between the two sensor elements.

6 flashes

Tank leakage detected 

by accessory module.

Control recovers after receiving 

message from accessory module.

7 flashes

Electronics Failure

Replace control module.

8 Flashes

This is just a warning; 

The control does not 

see power decaying 

with the knob in the 

OFF position.

Check valves.

Solid ON

Not an error—

indicates that the 

control is in OFF 

mode.

None; wait until LED turns off if you 

want to restart the system.

Summary of Contents for WV8840A

Page 1: ... is shown on the product label Inlet Pressure Range See appliance rating plate for inlet pressure range recommendation 1 2 PSI 14 0 in w c maximum inlet pressure allowed for proper operation Body Pattern 90 degrees with 1 2 in inlet and 1 2 in inverted flare outlet Mounting Mounting in upright position only Control Input Voltage Minimum 350 mV dc open circuit Voltage Maximum 850 mV dc open circuit...

Page 2: ...l or agricultural applications protect the control with a cover Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide covers for the control to limit contamination Heat Excessively high temperature can damage the control Make sure the maximum ambient temperature at the control does not exceed the rating ...

Page 3: ...1 Use a new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Ensure that gas supply is turned off 3 Run pipe or tubing to the water heater control If tubing is used obtain a tube to pipe coupling to connect the tubing to the control 4 Install a sediment trap in the supply line to the wa...

Page 4: ...t of 1 2 in pipe with 5 in w c pressure 2 Depress the piezo igniter to light the pilot flame and hold the knob in until the status indicator starts to blink approximately 30 seconds indicating pilot now being held by electronics NOTE LED should blink once every three seconds If not check the error codes in Table 3 3 Release the knob and turn to the desired temperature setting The burner will come ...

Page 5: ...ow rate 1 Check the full rate manifold pressure listed on the appliance nameplate Water heater control full rate outlet pressure should match this rating 2 With burner operating check the water heater control flow rate using the meter clocking method or check pressure using a manometer connected to the outlet pressure tap on the water heater control See Fig 5 MAINTENANCE WARNING Fire or Explosion ...

Page 6: ...ronics is holding the Pilot Valve open and the Main Valve closed You can now turn the knob to a desired setpoint temperature LED will continue to flash 1 time every 3 seconds while in Idle mode no call for heat Strobe every 3 seconds Not an error indicates call for heat during normal operation Main valve open None Action required 2 flashes Low thermopile voltage main valve not turned ON Check ther...

Page 7: ...ed in event of any physical damage tampering bent terminals missing or broken parts stripped threads or evidence of exposure to heat WARNING Scalding Hazard Can cause burns severe injury or death Never move temperature setpoint knob past the HOT setting without checking water temperature at the faucet and readjusting until comfortably warm to the touch Consider the ages and health of all who will ...

Page 8: ...bove the previous temperature follow these instructions 1 Set the temperature setpoint knob to OFF 2 Turn off the main gas valve to the appliance 3 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow step 1 in the warning above If you DO NOT smell gas continue with the next step 4 Turn on the gas supply to the appliance 5 Restart the appliance by performing lighting p...

Reviews: