background image

RUNS, BUT TANK SHOWS NO BUILD UP

Cut off building air supply to eliminate possibility of

broken lines by closing supply valve on tank. If unit still
fails to build up, remove air intake filter. If still no
success, disconnect copper lines connected to intake
valves (3/4 HP and up). While the unit is running, no air
should be coming  out of the copper line. If air is coming
out of the line, the unloader pilot is stuck or defective.
It should be removed, cleaned and inspected. The un-
loader pilot is at the other end of the copper line. See
Parts List for details of unloader and pilot.

If unit is not equipped with unloading valves (1/4  to

1/2 HP are not), remove discharge tube and check for

air flow. Block with hand to check ability to build up.
If poor or no discharge air, disassemble and inspect valves.
If discharge is good, look for air leak between pump and
tank valve (cracked discharge tube, tank, etc).

BUILDS UP, BUT NOT COMPLETELY, OR TAKES

EXCESSIVE TIME

Cut off system by closing tank valve and check pump

up time (see Data Table II). Remove intake and recheck.
Disconnect copper line at intake valves (3/4 HP and up).

If air is coming out of line (while unit is running), dis-

assemble and clean unloader pilot located at other end

of line. See Parts List for details.

Another reason for poor delivery, in multicyclinder

units, could be  a valve unloader sticking. The valve un-
loaders can be checked by disconnecting the copper line
leading to them and removing the cover bolts. Tapping
with a blunt instrument such as the handle of a large
screwdriver or small hammer, will loosen the cover so it
may be lifted off. Carefully remove the diaphragm; this
will expose the piston cup which operates the unloader.
With the unit running, manually depress the piston.
There should be a distinct change in the intake sound
indicating the valve is  being held open. Slowly depressing
the piston, you should first feel the resistance of the
return spring, then the  piston  contacting the intake
valve, then the sound change  is you move the valve off

the seat. Use fingernails to remove this piston cup for
cleaning beneath, if necessary.

If the source of the trouble has still not been located,

remove and inspect intake and exhaust valves for dirt or
warpage. (NOTE: The head must be removed on the 1/2
HP unit to service valves as they are not removable.) The
piston top and cylinder walls can be inspected at this
time.

PUMP SLOWS, STALLS, OR GOES OUT ON OVER-
LOAD

This is probably the result of the pump seizing. Check

oil level (and pressure in 1 HP and up).

 

Check tank pres-

sure, should be 90 psi or lower. (On WP240  units, turn
off power to both motor-pump units.)

Remove belt and bleed down tank. Turn pump by

hand, it should turn freely. If it does, motor may be

defective. If it does not, it may be the pump or a
plugged aftercooler tube. Disconnect discharge tube and
turn pump by hand again. If still hard turning, problem
is internal to the pump. If it now turns freely, check
piping to tank for obstructions.

EXCESSIVE VIBRATION

Usually due to omission of vibration pads or an

uneven weight distribution on the pads. Check this by
shutting off unit and applying your weight to the dif-
ferent corners of the unit. Excessive rocking should be
shimmed out. In very uneven floors, adjustable levelers
may be needed.

Belt guards often produce a vibrating noise even

under normal operating conditions. Readjusting will
usually eliminate this.

In some cases, the normal operation of the com-

pressor is considered excessive noise or vibration. In
these cases a remote air intake, adjustable pads, and air
line vibration isolators may be required, Isolators are
stocked in the commercial warehouse.

PUMP REMOVAL AND REPLACEMENT

Shut off power, drain oil, and bleed down tank.

Remove belt guard, loosen motor mounts and remove

belt(s).

Remove aftercooler tube at pump end. If tube is type

which wraps around crankshaft, then remove both ends

and any hold down straps.

If flywheel is accessible, then remove at this time;

otherwise it can be removed afterward if necessary. The

1/2 HP unit is held on with a keyed shaft and setscrew

and will probably need a puller. All others use a split

hub and key and can be removed by removing hub bolts

and nuts and driving a wedge into split.

Remove pump intake filter and the unloader air

supply line  (3/4  HP and up). Remove pump hold down
bolts and remove pump. (CAUTION: If flywheel has not

7

75-7131

Summary of Contents for WP230A-M

Page 1: ...Maintenance Schedule 2 Maintenance 2 Troubleshooting 4 Repair 7 Parts List 10 Ordering Information 14 WP240 Wiring Diagrams 14 WP250 Refrigeration Drier Operation Check 16 Data Tables 17 Rev 7 77 J R W Form Number 75 7131 Commercial Div ...

Page 2: ...essor is installed in an extremely dirty or dusty atmosphere the filters may need to be changed more frequently The three month checks will indicate a need for more frequent replacement uincy units of 1 4 to 3 4 are splash lubricated P units and larger are pressure lubricated A dipstick is provided on all units for checking the oil level To check the oil level stop the pump remove the dipstick wip...

Page 3: ...ned in a nonflammable solvent or warm soapy water The 1 4 to 2 HP compressors manufactured after September 1974 have one piece replaceable filters These should be visually checked for foreign material build up A dirty filter causes excessive oil consumption and should be replaced FILTER CARTRIDGE The condition of the filter element may be checked by noting the line pressure after the filter if a g...

Page 4: ...practice If possible attach a card with the figures to the device Decreasing off periods with no change in the pressure range indicate an increase in air consumption Pump up times will increase also This can be caused by added devices or leaks Increasing pump up time with no change in the pressure range or off time indicates wear in the compressor and may warrant closer observation This is usually...

Page 5: ...eak clean the unit thoroughly and sprinkle the areas suspected with baby powder Make certain not to get any baby powder into the intake Recheck the device after several hours and the leak should be more easy to locate Excessive oil on the after cooler pipe or compressor head usually indicates air leaks Locate these with a soap and water solution when the unit is operating The un loaders should als...

Page 6: ...art make certain power is applied and fuses installed With W240 units checkout of electrical power application to the pump motor will differ with the operation requirements of each system See wiring diagrams If a voltage tester is available check for proper power at the motor terminals If no power trace wiring back towards the source to locate the problem CHECK FIRST AT THE PRESSURE SWITCH If ther...

Page 7: ... beneath if necessary If the source of the trouble has still not been located remove and inspect intake and exhaust valves for dirt or warpage NOTE The head must be removed on the 1 2 HP unit to service valves as they are not removable The piston top and cylinder walls can be inspected at this time PUMP SLOWS STALLS OR GOES OUT ON OVER LOAD This is probably the result of the pump seizing Check oil...

Page 8: ...ing removal The oil pump is factory ground as an assembly and partial replacement is not possible In the event that the pump or crank bearing which is part of the pump is deemed faulty it should be replaced as a unit The assembly is held by four bolts see Fig 4 front view The replacement does not include an oil gauge If needed it must be ordered separately After reinstallation the oil pressure mus...

Page 9: ...D EXHAUST VALVES UNLOADER The intake valves exhaust valves and unloader mechanisms can be disassembled for inspection clean ing or repair in all sizes except the 1 2 HP The 1 2 HP unit is a sealed assembly in the head In the event the valves are deemed defective in this unit replace the head assembly Quincy Part No 2400 X2P On the 1 4 HP unit remove the two valve locking nuts in the head and the v...

Page 10: ...ro Corp filter and Norgren regulator and relief valve To perform any maintenance and repair work on the PRV station first shut off air supply from tank Then bleed down system by manually operating the drain push red button on drain valve Note that all valves and dampers will return to their normal position The regulator and relief valve can now be removed and replaced or repaired in place with the...

Page 11: ...Intake and Exhaust Valves 1 2 HP Unit UNLOADER h YiBkF EXCEPT I HP QUINCY PT 7 4 8 3 X INTAKE VALVE ASSY EXHAUST VALVE ASSY 1945 3 4 1 1 2 HP 3 4 1 1 2 H P QUINCY 4610X QUINCY 1919 X Fig 15 WP230 Unloader Assembly 3 4 HP Units and Up INTAKE VALVE ASSY EXHAUST VALVE ASSY 1979 3 4 AND I l 2 HP 3 4 AND l l 2 HP QUINCY PT 6540X QUINCY PT 8133 Fig 16 WP240 Unloader Assembly 1HP Fig 17 Mechanical Unload...

Page 12: ... 7483 X INTAKE ASSEMBLY DISCHARGE ASSEMBLY WP230 QUINCY PT 6671XU QUINCY PT 6670X Fig 19 WP230F G bly 2 and 3 HP Units Fig 20 WP230H M 5 to 20 and 3 HP Head Assembly 240F and G 2 Typical PTM Pall Trinity Micro Filter PRV Arrange ment 0n 3 HP and Larger Units Filter PRV Station For 1 4 to 2 HP well Stations See Form No 75 2558 BY CUSTOMER TOP VIEW WALL OUNTED FRONT VIEW Fig 21 all Mounted ELEMENT S...

Page 13: ...PRV Parts List Fig 22 e MCC1001SU160Y 6 1 Valve l f b6154 6155 I 4 9 1 Cage 160 psi 305917 00106 q5 10 Bracket Tank 8350 8351 8352 4 Notes 1 Order from PTM 2 Order from Norgren 3 Obtain Locally 4 Order from Quincy 5 Order from Honeywell 13 75 713 1 ...

Page 14: ...number WP240 WIRING DIAGRAMS The two most common ways the WP240 Air Com pressor can be used are 1 Manual selection of first stage pump unit with automatic second stage backup See Figures 10 and 11 Honeywell M O D E L WP250 Colt Industries Quincy Compressor Division Quincy Illinois u s A ERlAL DATE CODE 1 1 J 75 7131 d Fig 23 PTM Pall Trinity Micro Parts Local distributor or Pall Trinity Micro Corp...

Page 15: ... 13 L2 _ L2 4 Ll L 2 LI 4 _ i 3 Ml COMP I 5 3 2 1 S E T P S 2 5 10 P S I B E L O W P S 1 5323 Fig 26 Manual Alternation with Automatic Backup for Fig 28 Automatic Alternation with Backup and Isolated Three Phase Units Quincy Wiring Package No Control Quincy Wiring Package No 1485A WP1582 120 Volt Control Only Fig 27 Automatic Alternation with Automatic Backup for Single Phase Units Only 6 0 HZ ALT...

Page 16: ...ing the correct power supply see name plate Feel condensate discharge outlet ahead of trap and as close to drier as possible The outlet should be cool to the touch about 40 to 45 F under all operational con ditions no flow to full capacity flow of compressed air If drier has not been running energize drier and check for gradual decrease in temperature at condensate outlet Conduction of cold throug...

Page 17: ... 70 480 70 480 70 480 70 480 70 480 70 480 60 415 60 415 60 415 60 415 90 620 90 620 90 620 90 620 90 620 90 620 90 620 90 620 100 690 100 690 100 690 1 100 690 Inlet Size NPT Compr 1 4 6 l 2 13 3 4 19 l 2 13 3 4 19 l l 4 31 l 1 4 31 2 50 2 50 2 50 I Note Part Numbers listed are Quincy numbers aOrder Replacement Elements from Honeywell Local Business Office bO to 60 psi 0 to 415 kPa on 7 l 2 to 20...

Page 18: ...P240D WP24OE WP240F WP240G Quincy Model No FFHX2 FFHlO6 FFHlO8 FFH210 FFH216 FFH230 FFH240 a Each WP240 model has two identical motor pump units Data specified is applicable to both units b UnIoader solenoid in aftercooler line c Order Replacement Elements from Honeywell Local Branch Office ...

Page 19: ......

Page 20: ...innati OH 513 948 4185 Cleveland OH 216 361 7373 Dallas TX TEXAS Austin TX 512 478 1788 WYOMING Casper WY 307 265 9374 or 1 800 443 8446 Toll Free NEBRASKA Omaha NB 402 331 3200 Columbus OH 214 387 5416 614 486 5971 X210 El Paso TX 915 533 9924 NEW HAMPSHIRE Dayton OH Bedford NH 513 237 4035 603 625 6502 Ft Worth TX 214 263 2311 Toledo OH NEW JERSEY 419 473 972 X214 Mt Laurel N J 609 234 2224 Youn...

Reviews: