background image

If it is impossible to get sufficient oil pressure, check

the oil pump and pressure gauge by unscrewing the
pressure gauge until oil seeps out around the threads
during operation of the compressor. This will indicate
that oil pressure is reaching the system and confirms
operation of the pressure gauge. The compressor requires
oil pressure to pump and to operate intake valve un-
loaders. Lack of pumping ability is a good indication of
loss of oil pressure. If oil appears at the threads of the
gauge and the oil pressure gauge indicates no pressure,
the gauge is probably faulty and should be replaced. If
no oil appears at the threads of the gauge, this is an
indication of possible oil pump failure.

If the oil pump must be replaced, refer to the “Oil

Pump Replacement” section for instructions on removal
and repair of the oil pump housing. In cases of low (not
zero) pressure, the cause may be excessive wear in the
pumping unit. Pump up time should be checked against

the table. Listen for unusual knocks which might indicate
worn bearings.

1/4 HP..

. . . . . . . . . . . . . . . . .

.OverYear

1/2 HP. . . . . . . . . . . . . . . . . . .

.OverYear

3/4 HP..

. . . . . . . . . . . . . . . . . .

Over Year

1 HP . . . . . . . . . . . . . . . . . . . . . .

*Over Year

1-1/2 HP..

. . . . . . . . . . . . . . . . .

*Over Year

2 H P  

. . . . . . . . . . . . . . . . . . . . . . .  

280Days

3HP . . . . . . . . . . . . . . . . . . . . . . .

190Days

5HP . . . . . . . . . . . . . . . . . . . . . . .

115Days

7-1/2 HP.

. . . . . . . . . . . . . . . . . . .

75Days

10 HP. . . . . . . . . . . . . . . . . . . . . . .

55 Days

15 HP

.......................

40Days

20

 

HP. . . . . . . . . . . . . . . . . . . . . . .  28 Days

2. Make certain the proper grade of oil is being used

AND THE COMPRESSOR IS NOT BEING OVER-
FILLED. Over filling always causes high oil con-
sumption Oil level should never be above the high
mark on the dipstick.

3. Check for leaks.

4, Check intake filter/piping and crankcase breather

valve for cleanliness and obstructions. Restricting
the intake air will cause higher oil consumption.

OIL LEAK

Most common oil leaks occur around screws and

gaskets. They generally can be corrected by tightening
the screw or replacing the gasket. If you are unable to
locate the source of the leak, clean the unit thoroughly
and sprinkle the areas suspected with baby powder.
Make certain not to get any baby powder into the intake.
Recheck the device after several hours and the leak
should be more easy to locate.

Excessive oil on the after cooler pipe or compressor

head usually indicates air leaks. Locate these with a soap
and water solution when the unit is operating. The un-
loaders should also be checked while the compressor is
in the “off” cycle because they are pressurized during
that time.

EXCESSIVE OIL CONSUMPTION

Oil consumption is a difficult problem to resolve and

the following steps should be taken before any repairs
begin.

1. Confirm the Complaint-Oil at the tank drain does

not necessarily indicate high oil consumption.
A 20 HP unit may consume a pint of oil in two
weeks and still be within specification, Since oil
is commonly available in quarts, the following is
the minimum number of days a quart should last

(assuming 50 percent or less operating cycle).

5. Check for excessive oil pressure or high percent

operation. If after performing the above, it is still
considered an oil consumer with no apparent ex-
ternal cause, then:

a. With the valve to the system closed, check

pump up and cycle pressures against the values
in the data table. Differences greater than 10
percent indicate worn parts.

b.  Remove valves (the l/2  HP unit does not have

removable valves so the head must be removed)
and examine piston top. Oil wetted is acceptable
but any accumulation of oil indicates a defective
pump  .

OISY PUMP

The most common rea son for a noisy pump is a loose

flywheel or motor pulley. Check these first; then check:

1. Oil pressure-if low, check pump as described above.

Lack of oil pressure may have caused bearing
damage.

2. Valve assemblies-make certain they are tight.

3. Wrist pin or connecting rod bearings-stop pump

and remove belts. Rotate pump back and forth a

couple of inches, using the flywheel. If knock can

be heard, it is probably a bad wrist pin or 

5

75-7131

Summary of Contents for WP230A-M

Page 1: ...Maintenance Schedule 2 Maintenance 2 Troubleshooting 4 Repair 7 Parts List 10 Ordering Information 14 WP240 Wiring Diagrams 14 WP250 Refrigeration Drier Operation Check 16 Data Tables 17 Rev 7 77 J R W Form Number 75 7131 Commercial Div ...

Page 2: ...essor is installed in an extremely dirty or dusty atmosphere the filters may need to be changed more frequently The three month checks will indicate a need for more frequent replacement uincy units of 1 4 to 3 4 are splash lubricated P units and larger are pressure lubricated A dipstick is provided on all units for checking the oil level To check the oil level stop the pump remove the dipstick wip...

Page 3: ...ned in a nonflammable solvent or warm soapy water The 1 4 to 2 HP compressors manufactured after September 1974 have one piece replaceable filters These should be visually checked for foreign material build up A dirty filter causes excessive oil consumption and should be replaced FILTER CARTRIDGE The condition of the filter element may be checked by noting the line pressure after the filter if a g...

Page 4: ...practice If possible attach a card with the figures to the device Decreasing off periods with no change in the pressure range indicate an increase in air consumption Pump up times will increase also This can be caused by added devices or leaks Increasing pump up time with no change in the pressure range or off time indicates wear in the compressor and may warrant closer observation This is usually...

Page 5: ...eak clean the unit thoroughly and sprinkle the areas suspected with baby powder Make certain not to get any baby powder into the intake Recheck the device after several hours and the leak should be more easy to locate Excessive oil on the after cooler pipe or compressor head usually indicates air leaks Locate these with a soap and water solution when the unit is operating The un loaders should als...

Page 6: ...art make certain power is applied and fuses installed With W240 units checkout of electrical power application to the pump motor will differ with the operation requirements of each system See wiring diagrams If a voltage tester is available check for proper power at the motor terminals If no power trace wiring back towards the source to locate the problem CHECK FIRST AT THE PRESSURE SWITCH If ther...

Page 7: ... beneath if necessary If the source of the trouble has still not been located remove and inspect intake and exhaust valves for dirt or warpage NOTE The head must be removed on the 1 2 HP unit to service valves as they are not removable The piston top and cylinder walls can be inspected at this time PUMP SLOWS STALLS OR GOES OUT ON OVER LOAD This is probably the result of the pump seizing Check oil...

Page 8: ...ing removal The oil pump is factory ground as an assembly and partial replacement is not possible In the event that the pump or crank bearing which is part of the pump is deemed faulty it should be replaced as a unit The assembly is held by four bolts see Fig 4 front view The replacement does not include an oil gauge If needed it must be ordered separately After reinstallation the oil pressure mus...

Page 9: ...D EXHAUST VALVES UNLOADER The intake valves exhaust valves and unloader mechanisms can be disassembled for inspection clean ing or repair in all sizes except the 1 2 HP The 1 2 HP unit is a sealed assembly in the head In the event the valves are deemed defective in this unit replace the head assembly Quincy Part No 2400 X2P On the 1 4 HP unit remove the two valve locking nuts in the head and the v...

Page 10: ...ro Corp filter and Norgren regulator and relief valve To perform any maintenance and repair work on the PRV station first shut off air supply from tank Then bleed down system by manually operating the drain push red button on drain valve Note that all valves and dampers will return to their normal position The regulator and relief valve can now be removed and replaced or repaired in place with the...

Page 11: ...Intake and Exhaust Valves 1 2 HP Unit UNLOADER h YiBkF EXCEPT I HP QUINCY PT 7 4 8 3 X INTAKE VALVE ASSY EXHAUST VALVE ASSY 1945 3 4 1 1 2 HP 3 4 1 1 2 H P QUINCY 4610X QUINCY 1919 X Fig 15 WP230 Unloader Assembly 3 4 HP Units and Up INTAKE VALVE ASSY EXHAUST VALVE ASSY 1979 3 4 AND I l 2 HP 3 4 AND l l 2 HP QUINCY PT 6540X QUINCY PT 8133 Fig 16 WP240 Unloader Assembly 1HP Fig 17 Mechanical Unload...

Page 12: ... 7483 X INTAKE ASSEMBLY DISCHARGE ASSEMBLY WP230 QUINCY PT 6671XU QUINCY PT 6670X Fig 19 WP230F G bly 2 and 3 HP Units Fig 20 WP230H M 5 to 20 and 3 HP Head Assembly 240F and G 2 Typical PTM Pall Trinity Micro Filter PRV Arrange ment 0n 3 HP and Larger Units Filter PRV Station For 1 4 to 2 HP well Stations See Form No 75 2558 BY CUSTOMER TOP VIEW WALL OUNTED FRONT VIEW Fig 21 all Mounted ELEMENT S...

Page 13: ...PRV Parts List Fig 22 e MCC1001SU160Y 6 1 Valve l f b6154 6155 I 4 9 1 Cage 160 psi 305917 00106 q5 10 Bracket Tank 8350 8351 8352 4 Notes 1 Order from PTM 2 Order from Norgren 3 Obtain Locally 4 Order from Quincy 5 Order from Honeywell 13 75 713 1 ...

Page 14: ...number WP240 WIRING DIAGRAMS The two most common ways the WP240 Air Com pressor can be used are 1 Manual selection of first stage pump unit with automatic second stage backup See Figures 10 and 11 Honeywell M O D E L WP250 Colt Industries Quincy Compressor Division Quincy Illinois u s A ERlAL DATE CODE 1 1 J 75 7131 d Fig 23 PTM Pall Trinity Micro Parts Local distributor or Pall Trinity Micro Corp...

Page 15: ... 13 L2 _ L2 4 Ll L 2 LI 4 _ i 3 Ml COMP I 5 3 2 1 S E T P S 2 5 10 P S I B E L O W P S 1 5323 Fig 26 Manual Alternation with Automatic Backup for Fig 28 Automatic Alternation with Backup and Isolated Three Phase Units Quincy Wiring Package No Control Quincy Wiring Package No 1485A WP1582 120 Volt Control Only Fig 27 Automatic Alternation with Automatic Backup for Single Phase Units Only 6 0 HZ ALT...

Page 16: ...ing the correct power supply see name plate Feel condensate discharge outlet ahead of trap and as close to drier as possible The outlet should be cool to the touch about 40 to 45 F under all operational con ditions no flow to full capacity flow of compressed air If drier has not been running energize drier and check for gradual decrease in temperature at condensate outlet Conduction of cold throug...

Page 17: ... 70 480 70 480 70 480 70 480 70 480 70 480 60 415 60 415 60 415 60 415 90 620 90 620 90 620 90 620 90 620 90 620 90 620 90 620 100 690 100 690 100 690 1 100 690 Inlet Size NPT Compr 1 4 6 l 2 13 3 4 19 l 2 13 3 4 19 l l 4 31 l 1 4 31 2 50 2 50 2 50 I Note Part Numbers listed are Quincy numbers aOrder Replacement Elements from Honeywell Local Business Office bO to 60 psi 0 to 415 kPa on 7 l 2 to 20...

Page 18: ...P240D WP24OE WP240F WP240G Quincy Model No FFHX2 FFHlO6 FFHlO8 FFH210 FFH216 FFH230 FFH240 a Each WP240 model has two identical motor pump units Data specified is applicable to both units b UnIoader solenoid in aftercooler line c Order Replacement Elements from Honeywell Local Branch Office ...

Page 19: ......

Page 20: ...innati OH 513 948 4185 Cleveland OH 216 361 7373 Dallas TX TEXAS Austin TX 512 478 1788 WYOMING Casper WY 307 265 9374 or 1 800 443 8446 Toll Free NEBRASKA Omaha NB 402 331 3200 Columbus OH 214 387 5416 614 486 5971 X210 El Paso TX 915 533 9924 NEW HAMPSHIRE Dayton OH Bedford NH 513 237 4035 603 625 6502 Ft Worth TX 214 263 2311 Toledo OH NEW JERSEY 419 473 972 X214 Mt Laurel N J 609 234 2224 Youn...

Reviews: