Valve Actuator
90
customer.honeywell.com
70-6925
MP958 Pneumatic Valve Actuators
The MP958 Pneumatic Valve Actuator is direct-acting and used
only with Honeywell V5852A2xx, V5862A2xx, V5853A2xx, and
V5863A2xx Terminal Unit Valves to control hot and/or chilled
water.
Dimensions in inches (millimeters)
Actuator Type:
Valve
Action:
Direct Acting
Fail Safe Mode:
Spring Return
Air Connections:
Barbed fitting for 1/4 in. O.D. plastic tubing
Maximum Operating Pressure:
30 psi
1 1/4
(32)
2 1/4 DIA
1
1-1/4 IN. (32 MM) MINIMUM CLEARANCE TO REMOVE
ACTUATOR. 2-1/4 IN. (57 MM) MINIMUM CLEARANCE
TO FACILITATE STRAIGHT ON TUBING CONNECTION.
IF CLEARANCE IS LESS THAN 2-1/4 IN. (57 MM), USE
AN ELBOW.
1
VALVE
SIZE
A
IN. (MM)
1/2 in. NPT
3/4 in. NPT
3-3/16 (81)
3-1/8 (79)
A
C8106A
Product Number
Actuator
Force
Spring Range
Comments
(psi)
(kPa)
MP958A1009
Low
2 psi to 5 psi
14 kPa to 35 kPa
Only works with V5852A2xx, V5862A2xx, V5853A2xx, V5863A2xx
MP958A1017
Low
3 psi to 10 psi
21 kPa to 69 kPa
Only works with V5852A2xx, V5862A2xx, V5853A2xx, V5863A2xx
MP958A1025
Low
8 psi to 11 psi
55 kPa to 76 kPa
Only works with V5852A2xx, V5862A2xx, V5853A2xx, V5863A2xx