70-6925
7
Application Type:
Unit Ventilator
Dimensions, Approximate:
4 3/4 in. high x 3 3/4 in. wide x 3 in. deep
(121 mm high x 95 mm wide x 76 mm deep)
Airflow Usage:
0.022 scfm (10.4 mL/s) with 0.007 in. restriction
Air Connections:
Barb fittings 1/4 in. (6 mm)
Mounting:
In compartment of a unit ventilator
Operating Temperature:
135 F maximum (57 C maximum)
Storage Temperature:
150 F maximum (66 C maximum)
Remote Bulb:
Yes
Sensor Element:
Bulb 1/2 x 5 7/8 in., capillary 36 in. (914 mm) long
Setpoint:
Single
Number of Pipes:
2
Maximum Operating Pressure:
25 psi (170 kPa)
Accessories:
107324A
Capillary Holder Assembly for duct insertion, 8 3/8 in. long
14004376-001
Gasket for 14004378 Connector Assembly
14004378-002
Connector Assembly, with integral 0.005 in. restriction
and filters for post 1984 units
Replacement Parts:
14003113-002
Repair kit containing 0.007 in. restrictor plate, filters, and
gaskets for pre-1984 units
Product Number
Action
Sensor Element
Setpoint
Temperature
Range
Changeover
Throttling
Range
Includes
Comments
(F)
(C)
(psi)
(kPa)
(F)
(C)
LP916A1019
Direct
Acting
Bulb 1/2 x 5 7/8 in.,
capillary 36 in.
(914 mm) long
65 F to
85 F
19 C to
30 C
—
—
3.5 F 2 C Integral Mounting Bracket
and 304528A Bag
Assembly (mounting
hardware). Order bulb
hangers (316297-00021)
separately.
—
LP916A1134
Direct
Acting
Bulb 3/8 x 7 in.,
capillary 36 in.
(914 mm) long
65 F to
85 F
19 C to
30 C
—
—
3.5 F 2 C Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
—
LP916A1175
Direct
Acting
Bulb 3/8 x 7 in.,
capillary 36 in.
(914 mm) long
40 F to
80 F
—
—
—
7 F
—
Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
—
LP916B1017
Direct
Acting
Heating,
Reverse
Acting
Cooling
Bulb 1/2 x 5 7/8 in.,
capillary 36 in.
(914 mm) long
65 F to
85 F
19 C to
30 C
Heat 18 psi,
Cool 13 psi
Heat 124 kPa,
Cool 90 kPa
3.5 F 2 C Integral Mounting Bracket
and 304528A Bag
Assembly (mounting
hardware). Order bulb
hangers (316297-00021)
separately.
—
LP916B1058
Direct
Acting
Heating,
Reverse
Acting
Cooling
Bulb 1/2 x 5 7/8 in.,
capillary 36 in.
(914 mm) long
65 F to
85 F
19 C to
30 C
Heat 18 psi,
Cool 9 psi
Heat 124 kPa,
Cool 62 kPa
3.5 F 2 C Integral Mounting Bracket
and 304528A Bag
Assembly (mounting
hardware). Order bulb
hangers (316297-00021)
separately.
—
LP916B1074
Direct
Acting
Heating,
Reverse
Acting
Cooling
Bulb 3/8 x 7 in.,
capillary 36 in.
(914 mm) long
65 F to
85 F
19 C to
30 C
Heat 18 psi,
Cool 13 psi
Heat 124 kPa,
Cool 90 kPa
3.5 F 2 C Order Mounting Bracket,
Knob, Bulb Hangers, and
Scale Plate separately.
—
LP916B1082
Direct
Acting
Heating,
Reverse
Acting
Cooling
Bulb 3/8 x 7 in.,
capillary 36 in.
(914 mm) long
65 F to
85 F
19 C to
30 C
Heat 18 psi,
Cool 13 psi
Heat 124 kPa,
Cool 90 kPa
3.5 F 2 C Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
New
installation
model
LP916B1090
Direct
Acting
Heating,
Reverse
Acting
Cooling
Bulb 3/8 x 9 in.,
capillary 36 in.
(914 mm) long
65 F to
85 F
19 C to
30 C
Heat 18 psi,
Cool 13 psi
Heat 124 kPa,
Cool 90 kPa
3.5 F 2 C Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
—
LP916C1023
Reverse
Acting
Bulb 3/8 x 9 in.,
capillary 36 in.
(914 mm) long
60 F to
80 F
—
—
—
3.5 F —
Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
—