Temperature Controllers
36
customer.honeywell.com
70-6925
Airflow Usage:
0.07 scfm (33.0 mL/s) with 1 psi (7kPa) pressure drop
at 18 psi (124 kPa) main air supply
Connections:
Air: Combination 5/32 in. by 1/4 in. barb. Optional
accessory 14003755-001 (barb fitting for port 4,6,7, or 8 for all
RP920).
Input Signal:
3 to 15 psi (21 to 103 kPa)
Maximum Operating Temperature:
130 F (54 C)
Temperature Range:
40 F to 130 F (5 C to 55 C)
Maximum Operating Pressure:
30 psi (207 kPa)
Humidity Ratings:
5 to 95% RH
Remote Bulb Sensor:
no
Remote Control Point Adjustment:
Yes
Comments:
All RP920s can be converted to reverse acting in the field.
For additional technical information see literature Form no. 85-0224
and 95-7392EF.
Accessories:
14000786-001
Receiver Gauge, 25 F-125 F scale, 1 1/2 in. diameter, 1/
8 in. NPT connection
14000786-003
Receiver Gauge, 15 to 75% RH scale, 1 1/2 in.
diameter, 1/8 in. NPT connection
14000786-004
Receiver Gauge, 65 to 95% RH scale, 1 1/2 in.
diameter, 1/8 in. NPT connection
14000786-005
Receiver Gauge, 15 to 85% RH scale, 1 1/2 in.
diameter, 1/8 in. NPT connection
14000786-002
Receiver Gauge, -5 to 55 C scale, 1 1/2 in. diameter, 1/8
in. NPT connection
14004267-001
Temperature and Humidity scaleplate insert for setpoint
knob for all RP920
14004322-001
DIN Rail Mount
14505694-003
13 3/4 inch (350 mm) long mounting rail for RP920
14505694-004
17 3/4 inch (450 mm) long mounting rail for RP920
43188057-010
Clear plastic cover for all RP920A pneumatic controllers
43188123-010
Clear plastic cover for all RP920B, RP920C, RP920D
pneumatic controllers
305616
1-1/2 in. diameter, 1/8 NPT center stem back mount Receiver
gauge (0 to 2 in. w.c. scale) with +/- 2% accuracy
305965
1-1/2 in. diameter, 1/8 NPT center stem back mount Pressure
Indicating gauge (0 to 30 psi scale) with +/- 4% accuracy
305929
1-1/2 in. diameter, 1/8 NPT center back stem mount Receiver
gauge (-40 to +160 F scale) with +/- 2% accuracy
305930
1-1/2 in. diameter, 1/8 NPT center back stem mount Receiver
gauge (0 to 200 F scale) with +/- 2% accuracy
305931
1-1/2 in. diameter, 1/8 NPT center back stem mount Receiver
gauge (40 to 240 F scale) with +/- 2% accuracy
305972
Receiver gauge, 1-1/2 in. 1/8 NPT center back, temperature 50
to 100F
305986
Receiver Gauge. -20 to 80 F scale 1-1/2 in. diameter,1/2 NPT
connection
Replacement Parts:
14004277-003
Setpoint module with gasket with CPA for RP920
14004278-002
Compensation module with gasket for RP920B and
RP920D
14004533-001
Connector block with gasket and CPA for RP920
14003757-001
Seal screw for port 8 and O-ring repair parts for RP920
43915905-110
O-ring for filter in RP920
43188059-001
Setpoint knob for all RP920 pneumatic controllers
14002172-001
Gage Tap repair Plug
14001865-001
Filter Cartridge Assembly
Product Number
Application Action
Capacity
Number of
Sensors
Output Pressure Range
Includes
(psi)
(kPa)
RP920A1025
Proportional
pneumatic
controller
Direct
Acting
at 18 psi (124 kPa) MLP and
8.5 psi (59 kPa) BLP (does
not include sensor usage):
0.021 scfm (10 mL/s)
single
3 to 13 psi, output
signal maximum is
Mainline Pressure
minus 1/2 psi
21 to 90 psi, output
signal maximum is
Mainline Pressure
minus 7 kPa
With remote
control point
adjustment
capability.
RP920A1033
Proportional
pneumatic
controller
Direct
Acting
at 18 psi (124 kPa) MLP and
8.5 psi (59 kPa) BLP (does
not include sensor usage):
0.021 scfm (10 mL/s)
single
3 to 13 psi, output
signal maximum is
Mainline Pressure
minus 1/2 psi
21 to 90 psi, output
signal maximum is
Mainline Pressure
minus 7 kPa
Without remote
control point
adjustment
capability.
RP920B1023
Proportional
pneumatic
controller
Direct
Acting
at 18 psi (124 kPa) MLP and
8.5 psi (59 kPa) BLP (does
not include sensor usage):
0.046 scfm (21.7 mL/s)
dual
3 to 13 psi, output
signal maximum is
Mainline Pressure
minus 1/2 psi
21 to 90 psi, output
signal maximum is
Mainline Pressure
minus 7 kPa
With remote
control point
adjustment
capability.
RP920B1031
Proportional
pneumatic
controller
Direct
Acting
at 18 psi (124 kPa) MLP and
8.5 psi (59 kPa) BLP (does
not include sensor usage):
0.046 scfm (21.7 mL/s)
dual
3 to 13 psi, output
signal maximum is
Mainline Pressure
minus 1/2 psi
21 to 90 psi, output
signal maximum is
Mainline Pressure
minus 7 kPa
Without remote
control point
adjustment
capability.
RP920C1021
Proportional
plus integral
pneumatic
controller
Direct
Acting
at 18 psi (124 kPa) MLP and
8.5 psi (59 kPa) BLP (does
not include sensor usage):
0.021 scfm (10 mL/s)
single
3 to 13 psi, output
signal maximum is
Mainline Pressure
minus 1/2 psi
21 to 90 psi, output
signal maximum is
Mainline Pressure
minus 7 kPa
With remote
control point
adjustment
capability.
RP920C1039
Proportional
plus integral
pneumatic
controller
Direct
Acting
at 18 psi (124 kPa) MLP and
8.5 psi (59 kPa) BLP (does
not include sensor usage):
0.021 scfm (10 mL/s)
single
3 to 13 psi, output
signal maximum is
Mainline Pressure
minus 1/2 psi
21 to 90 psi, output
signal maximum is
Mainline Pressure
minus 7 kPa
Without remote
control point
adjustment
capability.
RP920D1029
Proportional
plus integral
pneumatic
controller
Direct
Acting
at 18 psi (124 kPa) MLP and
8.5 psi (59 kPa) BLP (does
not include sensor usage):
0.046 scfm (21.7 mL/s)
dual
3 to 13 psi, output
signal maximum is
Mainline Pressure
minus 1/2 psi
21 to 90 psi, output
signal maximum is
Mainline Pressure
minus 7 kPa
With remote
control point
adjustment
capability.
Summary of Contents for VP525C