background image

69-1493–1

6

T8400C ELECTRONIC THERMOSTAT

Table 1. Heating Cycle Rates.

Optional System Checkout

When in steps 2 and 3 only, the 

 key can be

used to turn heat or cool outputs on and off.
Change the SYSTEM switch setting to test heat
or cool outputs. No action takes place if the
SYSTEM switch is in the Off position.

Examples: System setting at HEAT: If heat is

on, the

 ▼

 key turns it off; if heat is

off, 

 turns it on.

System setting at COOL: If cool is
on, 

 key turns it off;  if cool is off,

 turns it on.

2. Press the 

▲▼ 

keys simultaneously for more than

one second to light all segments on display and to
enter installer setup mode. When the keys are
released, a two-digit software revision code is
displayed.

NOTE:

In installer setup mode only, each press of
the 

 key momentarily displays 01. Each

press of the 

 key momentarily displays

02. When the keys are released, these two-
digit codes are no longer displayed.

3. Press the 

▲ 

key. Factory information is displayed. A

typical example is shown, but information displayed
varies by model. This information is for factory use
only.

4. Press the 

▲ 

key again to display 

°

C or 

°

F.

System

Cycles Per Hour

Steam, Gravity

1

Hydronic Heat, Condensing Gas
Furnaces

a

3

Gas or Oil Forced Air

6

Electric Heat

9

Special Applications

b

12

5. Press the 

▼ 

key

 

to change the 

°

C or 

°

F indication.

6. Press the 

▲ 

key

 

 to display the heat cycle rate of 1,

3, 4, 5, 6, 9, or 12. If the desired cycle is displayed,
press the 

▲ 

key

 

to exit the installer setup mode. To

change the heat cycle rate, press the 

 key to scroll

between 1, 3, 4, 5, 6, 9, and 12. Stop scrolling when
the desired rate is displayed. See Table 1 for the
cycle rate options and the corresponding system
equipment.

a

High Efficiency Furnace.

b

Refer to equipment manufacturer’s instructions.

   NOTE: Steps 7 and 8 are available on select models.

7. Press the 

▲  

key to display cooling algorithm

configuration default.

M14684

M14685

M14690

M14686

M14687

M14688

M14689

M18419

8. Press the 

▲  

key to change cooling algorithm to C1

or C3.

C1 = Standard cooling algorithm.
C3 = Aggressive cooling algorithm (can cause
         overshooting).

9. Press the 

▲  

key to save all changes, exit installer

setup mode and return to normal operation.

NOTE:

After exiting installer setup mode, change the
setpoint to the desired room temperature.

CHECKOUT

Heating

1. Slide the SYSTEM switch to Heat and the FAN

switch to Auto.

2. Press and hold the 

 key to raise the temperature

setting several degrees above the room tempera-
ture. After approximately ten seconds, the heating
equipment should start. In conventional systems, the
system turns on the fan using a time delay relay or a
limit control. When using an electric heat thermostat,
the fan starts immediately.

3. Press the 

▼ 

key to lower the temperature setting

below the room temperature. Heating equipment
should stop.

4, 5, 12

Summary of Contents for TRADELINE T8400C

Page 1: ...ctronicThermostat INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check o...

Page 2: ...ions normally even when not level Mount wallplate with the screws provided see Fig 2 as follows 1 Place the wallplate at the desired location on the wall 2 Pull the thermostat wire through the wallplate entrance hole 3 Select the two mounting holes that best fit the application 4 Fasten the wallplate to the wall using the anchors and screws provided 5 After wiring the wallplate plug the hole to pr...

Page 3: ...g the T8400C Thermostat All wiring must comply with local electrical codes and ordinances Disconnect the power supply to prevent electrical shock or equipment damage NOTE To ensure proper mounting of thermostat restrict all wiring to the shaded area See Fig 4 The shape of the terminals permits insertion of straight or wraparound wiring connections either method is accept able See Fig 5 Fig 4 Restr...

Page 4: ...TION AS REQUIRED REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO TRANSFORMER SYSTEM CAN BE USED FOR CHANGEOVER VALVE ON SINGLE STAGE HEAT PUMP SYSTEMS POWER TO R TERMINAL IS REQUIRED WHEN THE SYSTEM SWITCH IS IN THE OFF POSITION 2 3 3 1 1 3 4 Fig 9 Mounting thermostat to wallplate L1 HOT L2 1 COOL CHANGEOVER FAN RELAY COOL RELAY HEAT RELAY 24V M13277A HEAT CHANGEOVER TRANSFORMER 1 POWER SUPPLY PROVI...

Page 5: ... setpoint and the room temperature are shown separately on the digital display The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed To set temperature setpoint 1 Select Heat or Cool by sliding the SYSTEM switch in the lower right corner of the thermostat to the desired mode See Fig 10 2 To display the temperature setpoints on the...

Page 6: ...indication 6 Press the key to display the heat cycle rate of 1 3 4 5 6 9 or 12 If the desired cycle is displayed press the key to exit the installer setup mode To change the heat cycle rate press the key to scroll between 1 3 4 5 6 9 and 12 Stop scrolling when the desired rate is displayed See Table 1 for the cycle rate options and the corresponding system equipment a High Efficiency Furnace b Ref...

Page 7: ...m temperature After approximately five minutes the cooling equipment should start The fan starts and stops with the cooling equipment 3 Press the key to raise the temperature setting above the room temperature Cooling system should shut down NOTE To bypass the five minute delay see Optional System Checkout section Fan 1 Slide the SYSTEM switch to Off and the FAN switch to On The fan should run con...

Page 8: ... Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Automation and Control Solutions Honeywell 1985 Douglas Drive North Golden Valley MN 55422 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www honeywell com yourhome ...

Reviews: