Honeywell TRADELINE T8400C Installation Instructions Manual Download Page 4

69-1493–1

4

T8400C ELECTRONIC THERMOSTAT

Mounting Thermostat to Wallplate

1. Engage the tabs at the top of the thermostat and

wallplate.

2. Swing down the thermostat and press the lower

edge of the thermostat onto the wallplate to latch.
See Fig. 9.

Fig. 7. Typical hookup of T8400C in heat-cool system

with two transformers.

Fig. 8. T8400C in one-stage heat, one-stage cool

wiring diagram with manual changeover.

Y

G

Rc

W

2

4     

R

B

O

M12562

L1
(HOT)

L2

FAN
RELAY

HEAT
RELAY

L1
(HOT)

L2

COMPRESSOR
CONTACTOR

HEATING 
TRANSFORMER

COOLING
TRANSFORMER

HEAT
DAMPER

COOL
DAMPER

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO TRANSFORMER 
SYSTEM.

CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
PUMP SYSTEMS.

POWER TO R TERMINAL IS REQUIRED WHEN THE SYSTEM SWITCH IS IN 
THE OFF POSITION.

2

3

3

1

1

3

4

Fig. 9. Mounting thermostat to wallplate.

L1 
(HOT)

L2

1

COOL
CHANGEOVER

FAN
RELAY

COOL
RELAY

HEAT
RELAY

24V

M13277A

HEAT
CHANGEOVER

TRANSFORMER

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

CAN BE USED FOR CHANGEOVER VALVE ON 
SINGLE-STAGE HEAT PUMP SYSTEMS.

FACTORY INSTALLED JUMPER.

2

3

2

2

Y

G

Rc

W

R

B

O

3

M14677A

SYSTEM

Cool  Off  Heat 

Auto  On

FAN

DASHED LINES INDICATE TABS
ON BACK OF THERMOSTAT

SYSTEM

Cool  Off  Heat

Auto  On

FAN

ENGAGE TABS  AT TOP  OF THERMOSTAT
WITH SLOTS ON MOUNTING PLATE.

PRESS LOWER EDGE OF 
CASE TO  LATCH.

A

B

Set

Room  

Set

Room  

Summary of Contents for TRADELINE T8400C

Page 1: ...ctronicThermostat INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check o...

Page 2: ...ions normally even when not level Mount wallplate with the screws provided see Fig 2 as follows 1 Place the wallplate at the desired location on the wall 2 Pull the thermostat wire through the wallplate entrance hole 3 Select the two mounting holes that best fit the application 4 Fasten the wallplate to the wall using the anchors and screws provided 5 After wiring the wallplate plug the hole to pr...

Page 3: ...g the T8400C Thermostat All wiring must comply with local electrical codes and ordinances Disconnect the power supply to prevent electrical shock or equipment damage NOTE To ensure proper mounting of thermostat restrict all wiring to the shaded area See Fig 4 The shape of the terminals permits insertion of straight or wraparound wiring connections either method is accept able See Fig 5 Fig 4 Restr...

Page 4: ...TION AS REQUIRED REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO TRANSFORMER SYSTEM CAN BE USED FOR CHANGEOVER VALVE ON SINGLE STAGE HEAT PUMP SYSTEMS POWER TO R TERMINAL IS REQUIRED WHEN THE SYSTEM SWITCH IS IN THE OFF POSITION 2 3 3 1 1 3 4 Fig 9 Mounting thermostat to wallplate L1 HOT L2 1 COOL CHANGEOVER FAN RELAY COOL RELAY HEAT RELAY 24V M13277A HEAT CHANGEOVER TRANSFORMER 1 POWER SUPPLY PROVI...

Page 5: ... setpoint and the room temperature are shown separately on the digital display The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed To set temperature setpoint 1 Select Heat or Cool by sliding the SYSTEM switch in the lower right corner of the thermostat to the desired mode See Fig 10 2 To display the temperature setpoints on the...

Page 6: ...indication 6 Press the key to display the heat cycle rate of 1 3 4 5 6 9 or 12 If the desired cycle is displayed press the key to exit the installer setup mode To change the heat cycle rate press the key to scroll between 1 3 4 5 6 9 and 12 Stop scrolling when the desired rate is displayed See Table 1 for the cycle rate options and the corresponding system equipment a High Efficiency Furnace b Ref...

Page 7: ...m temperature After approximately five minutes the cooling equipment should start The fan starts and stops with the cooling equipment 3 Press the key to raise the temperature setting above the room temperature Cooling system should shut down NOTE To bypass the five minute delay see Optional System Checkout section Fan 1 Slide the SYSTEM switch to Off and the FAN switch to On The fan should run con...

Page 8: ... Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Automation and Control Solutions Honeywell 1985 Douglas Drive North Golden Valley MN 55422 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www honeywell com yourhome ...