T8400C ELECTRONIC THERMOSTAT

Setting Fan Operation (Fuel) Switch

The fan operation (fuel) switch is preset at the factory in
the F position. See Fig. 3. This is the correct setting for
most systems. If this system is an electric heat system, set
the switch to the E position. The E setting allows the fan to
turn on immediately with the heating or cooling equipment
in a system where the G terminal is connected.

Fig. 1. Typical location of thermostat.

Mounting Wallplate to Wall

IMPORTANT

Level only for appearance. The thermostat
functions normally even when not level.

Mount wallplate with the screws provided (see Fig. 2) as
follows:

1. Place the wallplate at the desired location on the

wall.

2. Pull the thermostat wire through the wallplate

entrance hole.

3. Select the two mounting holes that best fit the

application.

4. Fasten the wallplate to the wall using the anchors

and screws provided.

5. After wiring the wallplate, plug the hole to prevent

drafts from affecting the thermostat.

Fig. 2. Mounting wallplate to wall.

5 FEET

[1.5 METERS]

YES

NO

NO

NO

M11338

M12202A

WALL

WALL  
ANCHORS (2)

WALLPLATE

WHEN USING WALL ANCHORS, DRILL 3/16 INCH 
HOLES FOR DRYWALL, 7/32 INCH HOLES FOR
PLASTER OR WOOD.

MOUNTING 
SCREWS (2)

1

1

M12580

FAN OPERATION (FUEL) SWITCH

F

E

Fig. 3. Fan operation (fuel) switch.

Summary of Contents for TRADELINE T8400C

Page 1: ...ctronicThermostat INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check o...

Page 2: ...ions normally even when not level Mount wallplate with the screws provided see Fig 2 as follows 1 Place the wallplate at the desired location on the wall 2 Pull the thermostat wire through the wallplate entrance hole 3 Select the two mounting holes that best fit the application 4 Fasten the wallplate to the wall using the anchors and screws provided 5 After wiring the wallplate plug the hole to pr...

Page 3: ...g the T8400C Thermostat All wiring must comply with local electrical codes and ordinances Disconnect the power supply to prevent electrical shock or equipment damage NOTE To ensure proper mounting of thermostat restrict all wiring to the shaded area See Fig 4 The shape of the terminals permits insertion of straight or wraparound wiring connections either method is accept able See Fig 5 Fig 4 Restr...

Page 4: ...TION AS REQUIRED REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO TRANSFORMER SYSTEM CAN BE USED FOR CHANGEOVER VALVE ON SINGLE STAGE HEAT PUMP SYSTEMS POWER TO R TERMINAL IS REQUIRED WHEN THE SYSTEM SWITCH IS IN THE OFF POSITION 2 3 3 1 1 3 4 Fig 9 Mounting thermostat to wallplate L1 HOT L2 1 COOL CHANGEOVER FAN RELAY COOL RELAY HEAT RELAY 24V M13277A HEAT CHANGEOVER TRANSFORMER 1 POWER SUPPLY PROVI...

Page 5: ... setpoint and the room temperature are shown separately on the digital display The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed To set temperature setpoint 1 Select Heat or Cool by sliding the SYSTEM switch in the lower right corner of the thermostat to the desired mode See Fig 10 2 To display the temperature setpoints on the...

Page 6: ...indication 6 Press the key to display the heat cycle rate of 1 3 4 5 6 9 or 12 If the desired cycle is displayed press the key to exit the installer setup mode To change the heat cycle rate press the key to scroll between 1 3 4 5 6 9 and 12 Stop scrolling when the desired rate is displayed See Table 1 for the cycle rate options and the corresponding system equipment a High Efficiency Furnace b Ref...

Page 7: ...m temperature After approximately five minutes the cooling equipment should start The fan starts and stops with the cooling equipment 3 Press the key to raise the temperature setting above the room temperature Cooling system should shut down NOTE To bypass the five minute delay see Optional System Checkout section Fan 1 Slide the SYSTEM switch to Off and the FAN switch to On The fan should run con...

Page 8: ... Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Automation and Control Solutions Honeywell 1985 Douglas Drive North Golden Valley MN 55422 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www honeywell com yourhome ...

Reviews: