Revision 4.0
STT850 Series HART/DE Option User’s Manual
Page 53
5.2.10 Procedure to Enter the Transmitter Tag
1.
From the
My Device
menu, make the following menu selections:
Shortcuts > Device Setup > Basic Setup > Device Information > Tag
.
2.
Click
Edit
. The
Tag
screen will be displayed.
3.
Key in the tag name (for example: STT850) which can be a maximum of eight characters.
4.
Click
OK
. The
Send to Device
screen will be displayed.
5.
Select the
Tag
check box.
6.
Click
Send
to download the change to the Transmitter, or Click
Return
to continue making
changes.
7.
5.2.11 Selecting the Process Variable (PV) Unit of Temperature Measurement
Engineering units affect the values of the LRV and URV. After changing the PV
engineering units to the Transmitter, verify changes to the units paramter, the LRV, and the
URV.
The Temperature measurement can be displayed in one of the pre-programmed engineering units.
1.
From
My Device
menu, make the following menu selections:
Shortcuts > Device Setup > Basic Setup > PV Units
2.
Click
Edit.
You will be warned that if you change the value of the variable it will change the
loop current, which may upset the control process.