850 Series HART/DE Option User’s Manual
Revision 4.0
Online/Device
Setup/Device Status
Overall Status
Displays a pictorial representation of the current
device status
Critical
Displays all possible Critical Status faults and
indicates OFF for inactive faults or ON for active
faults.
Help
– Critical
Diagnostics
Provides a more detailed description of each
Critical Status fault
Non-Critical
Displays the first set of possible Non-Critical
Status faults and indicates OFF for inactive faults
or ON for active faults.
Help
– Non-Critical
Diagnostics
Provides a more detailed description of each of
the first set of Non-Critical Status faults
Non-Critical
Displays the second set of possible Non-Critical
Status faults and indicates OFF for inactive faults
or ON for active faults.
Help
– Non-Critical
Diagnostics
Provides a more detailed description of each of
the second set of Non-Critical Status faults
Ext dev status
Displays all possible Extended Device Status
faults and indicates OFF for inactive faults or ON
for active faults.
Additional Status
Displays an advanced diagnostic detailed
breakdown of all Critical and Non-Critical faults
Online/Device
Setup/Diagnostics
Adv Diagnostics
Displays Advanced Diagnostics details for
tracking basic device operation. For more
detailed information on Advanced Diagnostics,
refer to HART Advanced Diagnostics section in
this Manual. Diagnostic information includes:
Installation and Device Life details
PV Tracking details
SV Tracking details
ET Tracking details
Operating Voltage details
AVDD Tracking details
Sensor CPU Temp. Tracking details
Power Up Diagnostics details
Config History
Displays a history of the last five configuration
parameters that have been changed.
Error Log
Available to enable and disable error logging.
If error log is enable all critical errors triggered
will be logged with a time stamp.