Page 38
STT
850 Series HART/DE Option User’s Manual
Revision 4.0
Online Menu Flow
Parameter menu/ name
Description/Valid values
Online/Device
Setup/Basic Setup/
Device Information
Honeywell Logo
Photograph of an STT850 Temperature
Transmitter
along with the official “Honeywell”
logo
Manufacturer
Displays Manufacturer of the STT850
Temperature Transmitter: Honeywell
International
Model
Displays Model number of the STT850
Temperature Transmitter: STT850
Install Date
Enter the date of site installation. This is a one-
time only configuration.
Tag
Enter tag identification up to eight alphanumeric
characters.
Long Tag
Enter a long tag name up to 32 alphanumeric
characters.
Cfg chng count
Configuration Change Counter
– this counter
keeps track of the number of times any
configuration parameter has been changed
Date
Enter a date for user information only.
Descriptor
Enter a descriptor for user information only (up
to 16 alphanumeric characters)
Message
Enter a message up to 32 alphanumeric
characters) that will be sent to the Display. The
message will be shown on the Display
interspersed with the configured screens. To
stop displaying the message, select “Clear
Display” in the Device Information menu.
Clear Message
Selecting this option clears the “Message” and it
will no longer be sent to the Display.
Range values
Displays all of the range information for the
device. The following limits are read only:
LRL: Lower range limit
URL: Upper range limit
LTL: Lower transducer limit
UTL: Upper Transducer limit
The following may be configured to desired zero
and span ranging for the application:
LRV: Lower Range Value (input which
represents 0% output)
URV: Upper Range Value(input which
represents 100% output)
Valid configurations for LRV and URV range
from LTL to UTL.
Model Number
Displays the full order model number of the
STT850 Temperature Transmitter