Page 34
STT750
Temperature Transmitter User’s Manual
Revision 4
6. Calibration
6.1.
Recommendations for Transmitter Calibration
The STT750 SmartLine Temperature Transmitter does not require periodic calibration to maintain
accuracy. Typically, calibration of a process-connected Transmitter will degrade, rather than augment
the capability of a smart Transmitter. For this reason, it is recommended that a Transmitter be
removed from service before calibration. Moreover, calibration must be accomplished in a controlled,
laboratory-type environment, using certified precision equipment.
6.2.
Calibration Procedures
For a Transmitter operating in analog mode, you must calibrate its output signal measurement range
using any compatible hand-held communicator or a local display.
One calibration option is to use the Honeywell MC Toolkit (MCT). Refer to the
MC Toolkit
(MCT202) User Manual,
# 34-ST-25-20 or
(MCT404) User Manual,
Document # 34-ST-25-50.
Calibration information and procedures for a Transmitter operating in the HART mode are provided
in the
STT750 Series HART Option User’s manual
, document number 34-TT-25-15, Section on
“Calibration.”
Summary of Contents for STT750 SmartLine
Page 51: ...Revision 4 STT750 Temperature Transmitter User s Manual Page 41 ...
Page 52: ...Page 42 STT750 Temperature Transmitter User s Manual Revision 4 ...
Page 53: ...Revision 4 STT750 Temperature Transmitter User s Manual Page 43 ...
Page 62: ...Page 52 STT750 Temperature Transmitter User s Manual Revision 4 ...
Page 63: ...Revision 4 STT750 Temperature Transmitter User s Manual Page 53 ...
Page 64: ...Page 54 STT750 Temperature Transmitter User s Manual Revision 4 ...
Page 65: ...Revision 4 STT750 Temperature Transmitter User s Manual Page 55 ...
Page 66: ...Page 56 STT750 Temperature Transmitter User s Manual Revision 4 ...