Page 12 of 14
4 LED Indication
Four LEDs are provided on the HART module for status indication, as follows:
D105 Yellow LED indicates fault or normal. Yellow on = Fault, Off=Normal.
D102 Green LED.
Solid Green = Hart is polled and response.
Off = not active.
D103 Green LED. Blinking Green = Heart Beat of the SS4 communication.
Solid Green or OFF = Waiting for SS4 to respond.
D104 Red LED. Solid Red = Alarm. Off = No Alarm.
5 HART Module Address
Polling address is assigned by rotary switch RSW1
(0,1,2,3,4,5,6,7,8,9,A,B,C,D,E,F).
Placing RSW1 to position 1,2,3.. to F, you are putting the devices in hardware
address mode. Hardware address will override software address.
Placing RSW1 to position 0, you are putting the devices in software addressing
mode. You can use command 6 to write polling address to the FSCHCOM
module. Once software polling address is written into the FSCHCOM, the
address is saved into flash memory until overwritten by next command
6 HART Module Mounting
If you have ordered Hart Module Option along with your SS4 , the HART module
is most likely already installed on the SS4 module.
If you have ordered HART module separately, remember to secure the HART
module to your SS4 module with two screws.