background image

The 

SIEMENS

 Model DB-ADPT detector/base adapter

interfaces Series 11 detectors with previously installed

DB-3S bases. For Series 3 air duct detector models

AD-3P, AD-3ILP, and SA-3P, use Series 11 Air Duct

Update Kit AD-11UK, which contains both the DB-ADPT and

the 

required 

DA-304 air duct cover for Series 11 detectors.

WARNING:

When replacing a detector with a different model, be

aware that existing detector accessories connected

to the base or air duct housing that were compatible

with the old detector may not be compatible with the

new  detector.  Always  read  the  Installation  Instruc-

tions accompanying the detector to determine detec-

tor and accessory compatibility.

P/N 315-094200-6

Installation  Instructions

Model DB-ADPT

Detector/Base Adapter

Fire Safety

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey  07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

Summary of Contents for DB-ADPT

Page 1: ...ifferent model be aware that existing detector accessories connected to the base or air duct housing that were compatible with the old detector may not be compatible with the new detector Always read the Installation Instruc tions accompanying the detector to determine detec tor and accessory compatibility P N 315 094200 6 Installation Instructions Model DB ADPT Detector Base Adapter Fire Safety S...

Page 2: ...apter will automatically stop and lock into place 4 To make the adapter to DB 3S interface tamperproof in the base use the Model DB LK 5 Install a Series 11 detector following the installation instructions included with the detector NOTE If it becomes necessary to remove the adapter push the adapter up into the base while rotating the adapter counterclockwise Continue to rotate counterclockwise un...

Page 3: ... Update Kit 1 Remove the sensing compartment cover from the existing duct housing 2 Remove the existing detector from the duct housing 3 To install the adapter into the duct housing rotate the adapter counterclockwise on the outer ring of the base located in the duct housing until the adapter drops into place ...

Page 4: ...ctions included with the detector and then install the new DA 304 sensing compartment cover Tighten the cover snugly but not so tightly as to warp cover and cause leakage around the edges NOTE If it becomes necessary to remove the adapter push the adapter down into the duct housing while rotating the adapter counterclockwise Continue to rotate counterclockwise until stop is reached Then pull upwar...