55
31-00282ES-01
Synchronization Check
Any modifications on the
Event Program wire sheet are detected by the control manager. Modifications can be any of the
following:
•
Added item
•
Deleted item
•
Moved item
•
Added connection
•
Deleted connection
•
etc.
As result, if working in ´on demand` teaching mode, all modified items will be not in sync with the application in the
controller and hence indicated by a yellow “warning” symbol on the item.
The application can be synchronized according to the active teaching mode, ´on demand` or ´immediate`. After
synchronization, the warning symbols are removed and the items are indicated in its synchronized state. When working
in teaching mode ´immediate` this happens immediately.
See also the
description of the “
Onboard IO
Shows the hardware configuration to which the application is designed for. The hardware displayed here, can differ from
the real hardware layout of the physical controller. For proper operation, the hardware of the project does not have to fit
100 % to the physical hardware of the used controller later. But, if the difference is too much, hardware compatibility is
not guaranteed. The control manager will show incompatibilities and software give support and tells what to do for
synchronicity.