background image

69-1059

9

SV9540; SV9640 SmartValve™ SYSTEM CONTROLS

1. Remove pilot adjustment cover screw. See Fig. 4.
2. Pilot adjustment is shipped at full flow rate.  Turn the

inner adjustment screw clockwise

if the inlet

pressure is too high. Turn the inner adjustment
screw clockwise           to decrease or counterclock-
wise           to increase pilot flame.

3. Replace the cover screw after the adjustment to

prevent gas leakage.

STARTUP AND CHECKOUT

Ignition System Control Switch Settings

Ignition system control switch settings are as follows:

OFF prevents pilot and main gas flow through the

ignition system control.

ON permits gas to flow through the control body. At the

appropriate time in the appliance operation, main
gas can flow to the main burner.

NOTE:

Controls are shipped with the ignition system
control switch in the ON position. If the appliance
is operated with the ignition system control switch
in the OFF position, the system will respond as if
the air proving switch is stuck in the no airflow
position.

Turn on Main Burner

Follow the instructions provided by the appliance manufac-
turer or turn up the thermostat to call for heat.

Perform Gas Leak Test

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH
Check for gas leaks with soap and water solution
any time work is done on a gas system.

CAUTION

Do not spray soap and water solution on the
SmartValve housing. Do not use an excessive
amount of soap and water solution to perform the
gas leak test. These can damage the control.

Gas Leak Test

1. Paint pipe connections upstream of the ignition

system control with rich soap and water solution.
Bubbles indicate a gas leak.

2. If a leak is detected, tighten the pipe connections.
3. Stand clear of the main burner while lighting to

prevent injury caused from hidden leaks that could
cause flashback in the appliance vestibule. Light the
main burner.

4. With the main burner in operation, paint the pipe

joints (including adapters) and the control inlet and
outlet with rich soap and water solution.

5. If another leak is detected, tighten the adapter

screws, joints, and pipe connections.

6. Replace the part if a leak cannot be stopped.

Check and Adjust Pilot Flame

The pilot flame should envelop 3/8 to 1/2 in. (10 to 13 mm)
of the tip of the flame rod. It should also be in continual
contact with the ground electrode. See Fig. 11. If the pilot
flame is small or lazy, or does not touch the ground
electrode, the inlet gas pressure may be too low, or the
pilot orifice may be partially clogged. Check and repair as
necessary. If the pilot flame is hard and noisy, the inlet gas
pressure may be too high. The ignition system control has
a pilot adjustment mechanism to reduce the pilot flow if
necessary. The pilot adjustment is shipped at the full pilot
gas flow rate. If pilot adjustment is necessary, proceed as
follows:

Fig. 11. Proper flame adjustment.

Check and Adjust Gas Input and
Burner Ignition

CAUTION

1.

Do not exceed input rating stamped on
appliance nameplate, or manufacturer’s
recommended burner orifice pressure for size
orifice(s) used. Make certain primary air
supply to main burner is properly adjusted for
complete combustion. Follow instructions of
appliance manufacturer.

2.

IF CHECKING GAS INPUT BY CLOCKING
GAS METER: Make certain there is no gas
flow through the meter other than to the
appliance being checked. Other appliances
must remain off with the pilots extinguished (or
that consumption must be deducted from the
meter reading). Convert flow rate to Btuh as
described in form 70-2602, Gas Controls
Handbook, and compare to Btuh input rating
on appliance nameplate.

3.

IF CHECKING GAS INPUT WITH MANOM-
ETER: Make sure the ignition system control
is in the OFF position before removing outlet
pressure tap plug to connect manometer
(pressure gauge). Also move the ignition
system control switch to the OFF position
when removing the gauge and replacing the
plug. Before removing inlet pressure tap plug,
shut off gas supply at the manual valve in the
gas piping to the appliance or, for LP, at the
tank. Also shut off gas supply before discon-
necting manometer and replacing plug.
Repeat Gas Leak Test at plug with main
burner operating.

NOTE:

Check the inlet pressure before adjusting the
pressure regulator.

PROPER FLAME 
ADJUSTMENT

HOT SURFACE
IGNITER 

FLAME ROD

M3350A

GROUND
ELECTRODE

3/8 TO 1/2 IN.
(10 TO 13 MM)

NOTE: GROUND ELECTRODE MUST NOT TOUCH FLAME
ROD (.050 IN. MINIMUM CLEARANCE). BEND GROUND
ELECTRODE IF NECESSARY. DO NOT BEND FLAME ROD.

Summary of Contents for SmartValve SV9540

Page 1: ...ication of the SmartValve System is the responsibility of the appliance manufacturer See Table 1 for temperature ranges and regulator types SPECIFICATIONS CAUTION The SV9540 SV9640 provide direct replacement only Use the Y8610 to convert standing pilot systems to electronic ignition systems Table 1 Model Number Suffix Letter Designation Model No Suffix Letter Ambient Temperature Range Pressure Reg...

Page 2: ...rs Angle and straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 5 Flange kits include one flange with attached O ring four mounting screws a 9 64 in hex wrench and instructions Approvals International Approval Services IAS Design Certified C2030025 Table 3 Capacityb of SV9540 SV9640 Model Size Inlet x Outlet in Capacity at 1 in wc pressure dropa c Minimum Regulated Capacity Maximum ...

Page 3: ... make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Follow these warnings exactly 1 Disconnect power supply before wiring to prevent electrical shock or equip...

Page 4: ... manifold IMPORTANT These ignition system controls are shipped with protective seals over the inlet and outlet tappings Do not remove the seals until ready to connect the piping Fig 2 Sediment trap installation Install Control 1 This ignition system control can be mounted 0 to 90 degrees in any direction including vertically from the upright position of the ignition system control switch 2 Mount t...

Page 5: ...NUT IS TIGHTENED TO PILOT BURNER M3346 Connect Pilot Gas Tubing 1 Cut tubing to the desired length and bend as necessary for routing to the pilot burner Do not make sharp bends or deform the tubing Do not bend the tubing at the ignition system control after the compression nut is tightened because this can result in gas leakage at the connection 2 Square off and remove burrs from the end of the tu...

Page 6: ...ith 120 Vac power supply connect the 120V hot lead to L1 on the ST9160 or 208907 Terminal Board With 240 Vac power supply there must be 120 Vac potential between L1 and appliance chassis 3 Appliance chassis must have reliable connection to earth ground 4 Connect control circuit to the ignition system control using the keyed connector See Fig 7 through 10 C1 C2 C3 40 VA TRANSFORMER CONT EAC HEAT HU...

Page 7: ... SWITCH COMBUSTION AIR BLOWER AIR DATA 1 2 L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY THERMOSTAT R R 24 VAC C W 208907 TERMINAL BOARD Q3450 IGNITER SENSOR SV9540 SV9640 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR 120 VAC INSTALLATIONS CONNECT THE 120V HOT LEAD TO L1 ON TERMINAL BOARD FOR 240 VAC INSTALLATIONS THERE MUST BE 120V BETWEEN L1 AND APPLIANCE CHASSIS AP...

Page 8: ...to the system thermostat Fig 10 SV9540 SV9640 typical boiler wiring diagram C1 C2 C3 40 VA TRANSFORMER L1 L2 LOAD COMMON THERMOSTAT 4 5 1 2 M12172 PRESSURE SWITCH NEUTRAL HOT L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY ROLL OUT SWITCH LIMIT SWITCH INDUCER BLOWER MOTOR R R W 24 VAC Q3450 IGNITER SENSOR AIR DATA SV9540 SV9640 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ...

Page 9: ...annot be stopped Check and Adjust Pilot Flame The pilot flame should envelop 3 8 to 1 2 in 10 to 13 mm of the tip of the flame rod It should also be in continual contact with the ground electrode See Fig 11 If the pilot flame is small or lazy or does not touch the ground electrode the inlet gas pressure may be too low or the pilot orifice may be partially clogged Check and repair as necessary If t...

Page 10: ...540 models see Table 3 for SV9640 capacities it may not be possible to deliver the desired outlet pressure This is an application issue not a control failure Take whatever steps are required to correct the situation 6 STEP OPENING PRESSURE REGULATORS ONLY Carefully check the burner lightoff at step pressure Make sure the burner lights smoothly and without flashback to the orifice Make sure all por...

Page 11: ...IGHTS AND FLAME IS SENSED DURING TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY MAIN VALVE OPENS IGNITER OFF FLAME SENSE LOST THERMOSTAT CALL FOR HEAT ENDS FIVE MINUTE WAIT PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN FLAME SENSE LOST MORE THAN FIVE TIMES IN THIS CALL FOR HEAT PREPURGE AIR PROVING SWITCH PROVED CLOSED WITHIN 30 SECONDS COMBUSTION AIR BLOWER OFF PILOT VALVE CLOSES PILOT IGNITE...

Page 12: ...wired or jumpered 3 Flashes Airflow proving switch remains open longer than 30 seconds after combustion air blower energized System goes into 5 minute delay period with combustion air blower off At the end of the 5 minute delay another ignition cycle will begin 1 Ignition system control switch must be in the ON position 2 Airflow proving switch operation tubing and wiring 3 Obstructions or restric...

Page 13: ...Airflow proving switch stuck closed 2 Airflow proving switch miswired or jumpered Combustion air blower is energized 3 Flash code does not come on after 30 seconds Wait for the prepurge time to expire 3 Flash code comes on 30 seconds after combustion air blower is energized Combustion air blower turns off 1 Ignition system control switch must be in the ON position 2 Airflow proving switch stuck in...

Page 14: ...tion 7 Replace the ignition system control access panel 8 Reconnect all electric power to the appliance 9 Set the thermostat to the desired setting 10 If the appliance does not turn on move the ignition system control switch to the OFF position and contact a qualified service technician for assistance Turning off the Appliance Vacation Shutdown Set the thermostat to the desired room temperature wh...

Page 15: ...69 1059 15 SV9540 SV9640 SmartValve SYSTEM CONTROLS ...

Page 16: ...d Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Helping You Control Your World 69 1059 C H 5 97 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Reviews: