SLN 700 SmartLine NCR Level Transmitter User’s Manual
Page 21
1.6 Maximum
Adjustment
Maximum Adjustment is used to set the gauge output when the level
is closest to the reference plane (highest liquid level). Together with
Minimum Adjustment, it determines the proportion of linear
correspondence of current output. Display in LCD is as follows.
When the menu number is 1.5, press
key to enter the maximum
adjustment. Display in LCD is as follows.
At this point, press
to edit the maximum adjustment.
1.7 Current
Output
This setting is used to set the current output mode.
4-20 mA means that low material level corresponds to 4 mA, while
high material level corresponds to 20 mA; 20-4 mA means that the
low level corresponds to 20mA, while the high level corresponds to
4mA. When the menu number is 1.6, press
key. Display in
LCD is as follows.
Press
key to select the wanted item and press
to confirm.
1.8 Sensor Tag
When the menu number is 1.7, press
key to move the menu to
the sensor tag display item. Display in LCD is as follows.
Press
to enter the status of parameter editing.
After editing, press
to confirm.
This is the end of the basic settings menu.
Maximum Adjustment
Current Output
Sensor Tag