Page 8
SLN 700 SmartLine NCR Level Transmitter User’s Manual
Revision 1
Installation position
During the installation, please note that the instrument should be kept minimal distance to tank
wall from the vessel wall. For different antenna, please refer to
However, the instrument must not under any circumstances be mounted closer than 200mm to
the vessel wall or values calculated from
1.
Reference plane
2.
Center of the vessel or symmetry axis
Figure 3-3: Installation position, >200 mm
Table 3-1: Minimal distance to tank wall
SLN700 Model
Min distance to tank wall
83A
1/5 × Tank Height
82A 82B 83B 83C
1/10 × Tank Height
82C 82D 83D 83E
87A 87B 87C 87D
1/20 × Tank Height