Honeywell Silent knight 5895XL Installation And Operation Manual Download Page 20

5895XL Manual - P/N 151142-L8:L  08/09/2017

17

Wiring Specifications

Before You Begin Installing

2.7.3  Wire Routing

You must follow power-limited wiring techniques, which includes maintaining one-quarter inch spacing between power-limited and 
non-power-limited circuits and separating high and low voltage circuits.

Figure 2.4  Wire Routing Example

5895XL Board

Summary of Contents for Silent knight 5895XL

Page 1: ...5895XL Intelligent Power Module Installation and Operation Guide Document 151142 L8 Rev L 08 09 2017 ECN 17 0387 ...

Page 2: ...arning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explo sions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reach...

Page 3: ...ith a normal room temperature of 15 27º C 60 80º F Verify that wire sizes are adequate for all initiating and indi cating device loops Most devices cannot tolerate more than a 10 I R drop from the specified device voltage Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to light ning induced transients Although no system is completely imm...

Page 4: ... this manual contact Silent Knight Technical Support at 800 446 6444 Please give the following information Product name and version number if applicable Printed manual Topic Title Page number for printed manual Brief description of content you think should be improved or corrected Your suggestion for how to correct improve documentation To order parts contact Silent Knight Sales at 800 328 0103 ...

Page 5: ...ice ID 21 3 4 Connecting SBUS Modules to the 5895XL 21 3 5 Flexputs I O Circuits 22 3 5 1 Conventional Notification Appliance 22 3 5 2 Releasing Operations 23 Class B Notification Wiring 23 Class A Notification Wiring 23 3 5 3 Conventional Initiation Circuits 24 Class B Inputs 24 Class A Inputs 24 3 5 4 Installing 2 Wire Smoke Detectors 25 3 5 5 Installing 4 Wire Smoke Detectors 26 3 5 6 Auxiliary...

Page 6: ...cates to the main FACP via the SBUS Each 5895XL provides an additional 6 000 feet of SBUS wiring length to the main panel As the drawings on the next pages illustrate this allows you to distribute modules SLC devices and outputs throughout an extremely large facility As well as expanding the wiring length capabilities the 5895XL also expands power capabilities by an additional 6 0 A of current 1 1...

Page 7: ...5895XL Manual P N 151142 L8 L 08 09 2017 3 Maximum Number of SBUS Modules Overview Figure 1 1 Example 5895XL Installation Overview ...

Page 8: ...Details Added 1 2 Agency Requirements The 5895XL has the same requirements as the main control panel These requirements are listed in the FACP Installation Manual Model Number FACP Installation Manual 5820XL EVS LS10061 001SK E 6820 EVS LS10144 001SK E 5700 151295 6700 LS10148 001SK E 5808 151274 L8 6808 LS10146 001SK E ...

Page 9: ...s with humidity generating equipment such as dryers production machinery When selecting a location to mount the 5895XL the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0 C 49 C 32 F 120 F or humidity outside the range of 10 93 at 30 C 86 F non condensing 2 3 Software Downloads In order to supply the latest features and functionality in fire alarm and lif...

Page 10: ...ating Voltage Current 1 L AC input hot 120 240 VAC 50 60 Hz 2 7 A 1 4 A 2 G Earth ground N A N A 3 N AC input neutral 120 240 VAC 50 60 Hz 2 7 A 1 4 A 4 X I O 6 Flexput Circuit 24 VDC 3 0 A Notification Circuits 5 O 100 mA Initiation Circuits 6 X I O 5 Flexput Circuit 24 VDC 3 0 A Notification Circuits 7 O 100 mA Initiation Circuits 8 X I O 4 Flexput Circuit 24 VDC 3 0 A Notification Circuits 9 O ...

Page 11: ...lay 1 24 VDC 2 5 A 28 C 29 N O 30 B SBUS IN OUT 5895XL communication with main panel or to controlling 5895XL if daisy chained 5 VDC 100 mA 31 A 32 MAIN 5895XL SBUS power from 5820XL 24 VDC 10 mA 33 Table 2 1 Terminal Strip Description and Electrical Ratings Terminal and Label Description Rating Voltage Current Table 2 2 Earth Fault Resistance Values by Terminal Function Terminal Number Terminal L...

Page 12: ...oad for the 5895XL based on 24 and 60 hours of standby The standby load calculations of line G in the Current Draw Calculation Worksheet Table 2 4 must be less than the number shown in Table 2 3 for the battery size used and standby hours required 2 6 2 Current Draw Worksheet For each 5895XL in the installation use Table 2 4 to determine current requirements during alarm battery standby operation ...

Page 13: ...tandby 1 3 mA mA Alarm 24 mA mA SK ZONE Aux Pwr Standby 12 mA mA Alarm 90 mA mA SLC Standby Alarm 27 mA mA mA SK ZONE 6 Aux Pwr Standby 50 mA mA Alarm 270 mA mA SLC Standby Alarm 2 mA mA mA SLC Modules B200SR Sounder Base Aux Pwr Standby 5 mA mA Alarm 35 mA mA SLC Standby 3 mA mA B200S Intelligent Sounder Base Aux Pwr Standby 5 mA mA Alarm high vol 35 mA mA SLC Standby 3 mA mA B200SR LF Low Freque...

Page 14: ...V 275 mA mA Alarm 70V 310 mA mA EVS VCM Voice Control Module 1 max Standby 70 mA mA Alarm 100 mA mA EVS SW24 Switch Expander 5 max Standby 10 mA mA Alarm 25 mA mA EVS RPU Remote Paging Unit 4 max Standby 70 mA mA Alarm 100 mA mA EVS LOC Local Operating Console includes 6860 RVM SW 24 4 max Standby 100 mA mA Alarm 150 mA mA EVS 100W 100W amplifier 4 max Standby Alarm 10 mA mA mA EVS 100WBU backup d...

Page 15: ...ion when SD SLC devices are installed 5 Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA Auxiliary Devices Current Notification Appliance Circuits Refer to device manual for current rating 5495 5499 Power Supply 24 VDC One input circuit 15 mA mA Both input circuits 30 mA mA Alarm mA mA Alarm mA mA Alarm mA mA Alarm mA mA Notification Appliances Current mA...

Page 16: ...mA 5860 Remote LCD Annunciator Standby 20 mA mA Alarm 25 mA mA 6855 Remote LCD Annunciator Standby 20 mA mA Alarm 25 mA mA 5824 Serial Parallel Printer Interface 4 max Standby Alarm 45 mA mA mA 5895XL Power Supply 16 max Standby Alarm 10 mA mA mA 5496 NAC Expander Standby Alarm 10 mA mA mA 5865 4 LED Annunciator Module with reset and silence switches 8 max Standby 35 mA mA Alarm 145 mA mA 5865 3 L...

Page 17: ...rk Cards SK NIC Network Interface Card 1 Max Standby Alarm 21 mA mA mA SK FML Fiber Optic Multi Mode 1 Max Standby Alarm 53 mA mA mA SK FSL Fiber Optic Single Mode 1 Max Standby Alarm 79 mA mA mA Auxiliary Devices3 Refer to devices manual for current rating IPDACT 2 IP Communicator 1 max Standby 93 mA mA Alarm 136 mA mA IPDACT 2UD IP Communicator 1 max Standby 98 mA mA Alarm 155 mA mA CELL MOD CEL...

Page 18: ...ted from the panel on a single wire run The table insures 6 0 volts of line drop maximum In general the wire length is limited by resistance but for heavier wire gauges capacitance is the limiting factor NOTE Total worst case current draw on a single SBUS cannot exceed 1 amp If a large number of accessory modules are required and the worst case current draw will exceed the 1 amp limit then the cur...

Page 19: ...ing Distance SBUS Modules to Panel Total Worst Case Current Draw amps 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0 100 1852 ft 4688 ft 6000 ft 6000 ft 0 200 926 ft 2344 ft 3731 ft 5906 ft 0 300 617 ft 1563 ft 2488 ft 3937 ft 0 400 463 ft 1172 ft 1866 ft 2953 ft 0 500 370 ft 938 ft 1493 ft 2362 ft 0 600 309 ft 781 ft 1244 ft 1969 ft 0 700 265 ft 670 ft 1066 ft 1687 ft 0 800 231 ft 586 ft 933 ft 1476 ft 0 ...

Page 20: ...Begin Installing 2 7 3 Wire Routing You must follow power limited wiring techniques which includes maintaining one quarter inch spacing between power limited and non power limited circuits and separating high and low voltage circuits Figure 2 4 Wire Routing Example 5895XL Board ...

Page 21: ...Power At installation connect the AC terminals to 120 VAC source as shown in Figure 3 5 It may be necessary for a professional electrician to make this connection The AC terminals are rated as 120 VAC 50 or 60 Hz 2 7 A Figure 3 5 AC Power Connection 3 2 Battery Connection The 5895XL battery charge capacity is 7 0 to 33 0 AH Use 12V batteries of the same AH rating Determine the correct AH rating as...

Page 22: ...ion 3 3 1 Figure 2 3 shows the location of the DIP switches on the 5895XL board 3 Configure the 5895XL module by adding it to the system through JumpStart or manually You can also assign a name to the module These procedures are described in the FACP Installation Manual Figure 3 7 Class B 5895XL Connection to FACP Red To Panel Black 12V Battery 12V Battery Battery Jumper P N 140694 Shipped With 58...

Page 23: ...l P N 151142 L8 L 08 09 2017 Hardware Installation Connecting the 5895XL to the FACP Figure 3 8 Class A 5895XL Connection to FACP See Figure 3 10 for SBUS Module Connections See Figure 3 10 for SBUS Module Connections ...

Page 24: ... location of the DIP switch on the board Figure 3 9 Possible Module Addresses 3 4 Connecting SBUS Modules to the 5895XL 1 Connect SBUS modules to the 5895XL as shown in Figure 3 10 or Figure 3 11 2 All SBUS modules must have an ID Use the DIP switches on the module board to assign an ID number 1 31 to the module This number identifies the module to the 5895XL and must be unique ...

Page 25: ...ircuits The six Flexput circuits are an innovative and versatile feature of the 5895XL panel They can be used as Class A or B notification circuits Class A or B initiation circuits either 2 or 4 wire detectors or as auxiliary power resettable continuous or door holder This section of the manual explains how to install conventional notification appliances and initiating devices to be used with the ...

Page 26: ...ll a Class B notification appliance circuit 1 Wire Class B Notification appliances as shown in Figure 3 12 2 Configure the circuit through programming Figure 3 12 Class B Notification Appliance Circuit Wiring Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual To install a Class A notification appliance circuit 1...

Page 27: ...s and pull stations directly to the I O circuits of the 5895XL panel To install a Class B switch 1 Wire the Class B switch as shown in Figure 3 14 2 Configure the circuit through programming see FACP Installation Manual Figure 3 14 Class B Input Switches Class A Inputs You can connect conventional Class A switches such as waterflow switches and pull stations directly to the I O circuits of the 589...

Page 28: ...e 3 16 and Figure 3 17 illustrate how to connect a UL listed 2 wire detector to the control panel Class B Installation To install a Class B two wire smoke detector wire as shown in Figure 3 16 Figure 3 16 Two Wire Class B Smoke Detector Note I O circuit 5 and 6 used as an example Any I O point pairing could be used NOTE In programming any point that uses multiple I O circuits are always referred t...

Page 29: ...onnected to the control panel at once 2 Each Class B loop input is paired with a unique power source as shown in Figure 3 18 3 Each loop gets smoke power from the even numbered I O circuit and the contact input is connected to the odd numbered I O circuit Figure 3 18 Class B 4 Wire Smoke Detector Connections Note I O circuit 5 and 6 used as an example Any I O point pairing could be used NOTE In pr...

Page 30: ... fire system is reset If AC power is not present the auxiliary door holder power will be disconnected to con serve the battery backup When AC power is restored power is immediately restored to the door holder circuits Constant Power Use constant power for applications that require a constant auxiliary power source Power is always present at Constant circuits Resettable Power Resettable power is ty...

Page 31: ...re alarm control panel Appliances which can be synchronized indicate the type of sync available in the columns marked Audio and or Visual Manufacturer Model Audio Visual Type AMSECO SH24W 153075 x x Horn Strobe SAD24 153075 x Strobe SAD24 75110 x Strobe SL24W 75110 x Strobe SL24C 3075110 x Strobe SLB24 75 x Strobe RSD24 153075 x Strobe RSD24 75110 x Strobe SH24W 75110 x x Horn Strobe SH24W 3075110...

Page 32: ... Strobe P241575K FC x x Horn Strobe P2430 FC x x Horn Strobe P2430W FC x x Horn Strobe P2430K FC x x Horn Strobe P2475 FC x x Horn Strobe P2475W FC x x Horn Strobe P2475K FC x x Horn Strobe P24110 FC x x Horn Strobe P24110W FC x x Horn Strobe P24110K FC x x Horn Strobe S2430W FC x Strobe S2430K FC x Strobe S2475 FC x Strobe S2475W FC x Strobe S2475K FC x Strobe S24110 FC x Strobe S24110W FC x Stro...

Page 33: ...575 x x Horn Strobe GCC24 x x Multi Candella Horn Strobe Ceiling Mount GCCR24 x Multi Candella Horn Strobe Ceiling Mount GCS24 x Multi Candella Strobe Ceiling Mount GCSR24 x Multi Candella Strobe Ceiling Mount GECR 24 x x Multi Candella Horn Strobe GES24 15 x Strobe GES24 30 x Strobe GES24 60 x Strobe GES24 75 x Strobe GES24 110 x Strobe GES24 15 75 x Strobe GES24 177 x Strobe GES3 24 x Multi Cand...

Page 34: ...trobe PC2R P x x 2 Wire Horn Strobe P2RH x x 2 Wire Horn Strobe High Candela P2RH P x x 2 Wire Horn Strobe High Candela PC2RH x x 2 Wire Horn Strobe High Candela PC2RH P x x 2 Wire Horn Strobe High Candela P2W x x 2 Wire Horn Strobe P2W P x x 2 Wire Horn Strobe PC2W x x 2 Wire Horn Strobe PC2W P x x 2 Wire Horn Strobe P2WH x x 2 Wire Horn Strobe High Candela P2WH P x x 2 Wire Horn Strobe High Cand...

Page 35: ...SP x x Horn Strobe 2W WHT Wall 4x4 PC2RL x x Horn Strobe 2W Red Ceil 4x4 PC2WL x x Horn Strobe 2W WHT Ceil 4x4 P2GRL x x Horn Strobe 2W Red Wall 2x4 P2GWL x x Horn Strobe 2W WHT Wall 2x4 P4RL x x Horn Strobe 4W Red Wall 4X4 P4WL x x Horn Strobe 4W WHT Wall 4X4 PC4RL x x Horn Strobe 4W Red Ceil 4X4 PC4WL x x Horn Strobe 4W WHT Ceil 4X4 SR x Strobe SR P x Strobe SCR x Strobe SCR P x Strobe SRH x Str...

Page 36: ... Strobe P2WH LF x x 2 Wire Low Frequency Sounder Strobe HR LF x Low Frequency Sounder HW LF x Low Frequency Sounder P Plain ALERT Pad Printing ALERT SP Fuego Wheelock AH 12 x Horn AH 24 x Horn AH 12WP x Horn Weatherproof AH 24WP x Horn Weatherproof AMT 241575W x x Multi Tone Horn Strobe AMT 24MCW x Mutli Tone Horn Strobe AMT 241575W NYC x x Multi Tone Horn Strobe AMT 12 24 x Multi tone Horn AMT 12...

Page 37: ... MultitoneHorn Strobe MT 241575W x x Multitone Horn Strobe MT 24MCW x Multitone Horn Strobe MTWP 2475W x Multitone Horn Strobe MTWP 2475C x Multitone Horn Strobe MTG 121575W x x Multitone Horn Strobe MTR 121575W x x Multitone Horn Strobe MTWPA 2475W x x Multitone Horn Strobe MTWPB 2475W x x Multitone Horn Strobe MTWPG 2475W x x Multitone Horn Strobe MTWPR 2475W x x Multitone Horn Strobe MTWPA 24MC...

Page 38: ... 2415C x Strobe RSSR 2475W x Strobe RSSR 2475C x Strobe RSSR 24110C x Strobe RSSA 24110W x Strobe RSSB 24110W x Strobe RSSG 24110W x Strobe RSSR 24110W x Strobe RSSA 24MCC x Multi Cd Strobe RSSB 24MCC x Multi Cd Strobe RSSG 24MCC x Multi Cd Strobe RSSR 24MCC x Multi Cd Strobe RSSWPA 2475W x Strobe Weatherproof RSSWPA 24MCCH x Strobe Weatherproof RSSWPG 24MCCH x Strobe Weatherproof RSSWPR 24MCCH x ...

Page 39: ...he maximum reset time of the smoke detec tor Table A 1 lists two wire smoke detectors that are compatible with the 5895XL panel The table is organized by manufacturer The col umns show the number of detectors per loop that can be used Wheelock cont ZRS MCWH x Strobe ZRS 24MCC x Strobe ZRS 24MCCH x Strobe MB G6 24 x Motor Bell MB G10 24 x Motor Bell MB G6 12 x Motor Bell MB G10 12 x Motor Bell MIZ ...

Page 40: ... 40 loop 611UD 601U or 602U S10 S00 S03 40 loop 611UT 601U or 602U S10 S00 S03 40 loop 612U 601U or 602U S10 S00 S03 40 loop 612UD 601U or 602U S10 S00 S03 40 loop 711U 701E or 701U N A S10A 25 loop 712U 701E or 701U N A S10A 25 loop 713 5U 702E or 701U N A S10A 25 loop 713 6U 702E or 701U N A S10A 25 loop 721 U S10A N A S10A 30 loop 721 UT S10A N A S10A 30 loop Kidde Fenwall PSD 7156 FE01A P56FE1...

Page 41: ...A N A 30 loop 2100T A N A 30 loop 2100TB A N A 30 loop 2100TS A N A 30 loop 2151 B110LP A N A 30 loop 2300T A N A 30 loop 2300 A N A 30 loop 2300TB A N A 30 loop 2400 A N A 30 loop 2400 DH400 A N A 30 loop 2400AIT A N A 30 loop System Sensor cont 2400AT A N A 30 loop 2400TH A N A 30 loop 2451 B401B A N A 30 loop 2451DH DH 400 A N A 30 loop 2451TH B401B A N A 30 loop 2800 A N A 30 loop 2800TH A N A...

Page 42: ...r 2112 24ATR Photoelectric 0 50 60 70 System Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24 D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelectric w 135 Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 Thermal Supervisory Relay 15 45 System Sensor 2312 24TB Photo...

Page 43: ...e Detectors Smoke Detector Base Detector Type Max Standby Current mA Alarm Current mA Table A 3 Compatible Door Holders Manufacturer Model Type Current mA Edwards DH150A Floor Mount 96 Edwards DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 Table A 4 Compatible Relays...

Page 44: ...andela Plain White SPSW ALERT Wall High Fidelity Speaker Strobe Amber Lens ALERT White SPSW CLR ALERT Wall High Fidelity Speaker Strobe Clear Lens ALERT White SPSW P Wall High Fidelity Speaker Strobe Plain Red SPSWH Wall High Fidelity Speaker Strobe High Candela White SPSWH P Wall High Fidelity Speaker Strobe High Candela Plain Red SPCRL Ceiling High Fidelity Speaker Red SPCWL Ceiling High Fidelit...

Page 45: ...uct back to customer via UPS ground Return the Honeywell product circuit board only Products that are returned in cabinets will be charged an additional 50 to cover the extra shipping and handling costs over board only returns Do not return batteries Honeywell has the authority to determine if a product is repairable Products that are deemed un repairable will be returned to the customer Product t...

Page 46: ...ANUFACTURER MAKES NO FURTHER WARRANTIES AND DISCLAIMS ANY AND ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF O...