10
5895XL Manual - P/N 151142-L8:L 08/09/2017
Before You Begin Installing
Calculating Current Draw and Standby Battery
SK-BEAM-T
3
(with integral test)
SLC
Standby/Alarm:
2
mA
mA
mA
Aux. Pwr
Standby: 2 mA
mA
Alarm:
8.5
mA
mA
SK-FIRE-CO
SLC
Standby:
.30
mA
mA
Alarm:
7.2
mA
mA
Addressable SLC Module
SK-MONITOR
Standby/Alarm:
.375
mA
mA
mA
SK-MINIMON
mA
mA
SK-PULL-SA
mA
mA
SK-PULL-DA
mA
mA
SK-MONITOR-2
Standby/Alarm:
.75
mA
mA
mA
SK-MONITOR-10
Standby/Alarm:
3.5
mA
mA
mA
SK-CONTROL
SLC
Standby:
.375
mA
mA
Alarm: .375 mA
mA
Aux Pwr
Standby:
1.
7 mA
mA
Alarm:
7 mA
mA
SK-CONTROL-6
SLC
Standby:
2.25
mA
mA
Alarm:
2.25
mA
mA
Aux Pwr
Standby:
8
mA
mA
Alarm:
20
mA
mA
SK-RELAY
Standby/Alarm:
.255
mA
mA
mA
SK-RELAY-6
Standby/Alarm:
1.45
mA
mA
mA
SK-RELAYMON-2
Standby:
1.3
mA
mA
Alarm:
24
mA
mA
SK-ZONE
Aux Pwr
Standby 12 mA
mA
Alarm 90 mA
mA
SLC
Standby/Alarm .27 mA
mA
mA
SK-ZONE-6
Aux Pwr
Standby 50 mA
mA
Alarm 270 mA
mA
SLC
Standby/Alarm 2 mA
mA
mA
SLC Modules
B200SR Sounder Base
Aux Pwr
Standby: .5 mA
mA
Alarm: 35 mA
mA
SLC
Standby .3 mA
mA
B200S Intelligent Sounder Base
Aux Pwr
Standby: 5 mA
mA
Alarm: (high vol) 35 mA
mA
SLC
Standby .3 mA
mA
B200SR-LF Low Frequency Sounder
Base
Aux Pwr
Standby: 1 mA
mA
Alarm: 125 mA
mA
B200S-LF Low Frequency Sounder
Base
Aux Pwr
Standby .55 mA
mA
Alarm (high vol) 140 mA
mA
SLC
Standby .30 mA
mA
B224RB Relay Base
Standby/Alarm: 0.5 mA
mA
mA
RTS151/151 KEY
Alarm: 7.5 mA
mA
RA100Z
Alarm: 10 mA
mA
SLC Isolator Devices
SK-ISO (Isolator Module)
(100 max/loop)
Standby/Alarm: .45 mA
mA
mA
B224BI Isolator Base
Standby/Alarm: .5 mA
mA
mA
Accessories Modules
Table 2.4 Current Draw Worksheet for SK SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
Summary of Contents for Silent knight 5895XL