T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355—1
12
Table 8. Thermostat Installer Setup Options
(Continued).
Installer Setup
Number
(Press
Unoccupied
Temp key
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Select
to change)
Display
Description
Display
Description
Setting
Intelligent Fan™
operation
17
2
Fan operates con-
tinuously in Occupied
and recovery modes.
Fan operates with call
for heating or cooling in
Unoccupied mode.
0 or 1
0—Fan only operates with calls for
heating or cooling in Occupied
and Unoccupied modes
1—Fan operates continuously in
Occupied mode. Fan operates
with calls for heating or cooling in
Unoccupied mode.
Not used
18
—
—
—
—
—
Extended fan
operation in
heating
a
19
0
No extended fan
operation after the call
for heat ends
1
Fan operation is extended
90 seconds after the call for
heat ends.
Extended fan
operation in
cooling
20
0
No extended fan
operation after the call
for cool ends
1
Fan operation is extended
90 seconds after the call for
cool ends.
Fan key adjust-
ment (models
with Fan key)
21
0
Fan setting key is
operational
1
Fan setting key is Auto only
Remote sensing
22
0
Remote sensing not
activated
1
Remote sensing activated
Temperature
averaging
network
b
23
0
Temperature averaging
disabled
1
Temperature averaging between
local sensor and remote sensor(s)
activated
Not used
24
—
—
—
—
—
Keypad lockout
level (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat)
25
0
No lockout
1 or 2
1—Lockout all keys on thermostat
except system and fan settings,
temporary setpoint, clock and
day adjustments
2—Lockout all keys except Set
Current Day/Time, increase
▲
and decrease
▼
keys
Duration of
temporary
override
26
3
3—Three hour override
1, 8 or 12 1—One hour override
8—Eight hour override
12—Twelve hour override
Not used
27 thru 29
—
—
—
—
—
Deadband
30
2
Heating and cooling
setpoints can be set no
closer than 2
°
F
3 thru 10 Heating and cooling setpoints can
be set no closer than the chosen
value
Interstage
control point
(Q7300C,D only)
31
0
Disabled
1 thru 12 Temperature has to change more
than the chosen value before the
system calls for the next stage.
(Example: 68
°
F is the heat setpoint,
2
°
F is the interstage setting,
temperature is 65.5
°
F, the second
stage turns on, brings the
temperature to 66
°
F and turns off.
The heat pump continues to run until
the setpoint is met.)
b
Number 22 must be set to 1 and remote sensor(s) must be installed.
(Continued)