T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355—1
13
Table 8. Thermostat Installer Setup Options
(Continued).
Installer Setup
Number
(Press
Unoccupied
Temp key
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Select
to change)
Display
Description
Display
Description
Setting
Minimum on time
32
2
2 minute minimum on
time for heating and
cooling
0 or 1
No minimum on time or
1 minute minimum on time for
heating and cooling
Minimum off
time for the
compressor
33
4
4 minute minimum off
time for the compressor
0, 1, 2, 3
or 5
Minimum number of minutes
(0 thru 5) the compressor will be off
between calls for the compressor
Temperature
range stops in
heating
34
90
Highest setpoint heating
can be set to
40 to 89 Temperature range (1
°
F increments)
heating setpoint can be set to
Temperature
range stops in
cooling
35
45
Lowest setpoint cooling
can be set to
46 to 99 Temperature range (1
°
F increments)
cooling setpoint can be set to
Not used
36
—
—
—
—
—
Temperature
display
adjustment
37
0
No difference in
displayed temperature
and actual room
temperature
1 thru 6
1—Display adjusts to 1
°
F higher
than actual room temperature
2—Display adjusts to 2
°
F higher
than actual room temperature
3—Display adjusts to 3
°
F higher
than actual room temperature
4—Display adjusts to 1
°
F lower than
actual room temperature
5—Display adjusts to 2
°
F lower than
actual room temperature
6—Display adjusts to 3
°
F lower than
actual room temperature
Minimum off
times in heating
38
4
4—4 minute minimum
off time
0, 1, 2, 3,
or 5
Minimum number of minutes
(0 thru 5) the heating equipment will
be off between calls for heat
Not used
39
—
—
—
—
—
Installer Setup
lockout (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat)
40
0
0—No Installer Setup
lockout
1
1—Installer Setup lockout activated