PX2 Series Heavy Duty Presssure Transducers
ISSUE 8
50052336
Table 4. Pressure Ratings
bar
kPa
MPa
psi
Operating
Pressure
Over-
pressure
Burst
Pressure
Operating
Pressure
Over-
pressure
Burst
Pressure
Operating
Pressure
Over-
pressure
Burst
Pressure
Operating
Pressure
Over-
pressure
Burst
Pressure
1
5
8
100
500
800
1
3.1
5.1
15
70
115
1.6
5
8
160
1000
1700
1.6
5.2
8.6
30
150
250
2
10
17
250
1000
1700
2.5
6.9
10.3
50
250
400
2.5
10
17
400
1700
2700
4
6.9
10.3
100
450
750
4
17
27
600
3100
5100
4.6
6.9
10.3
150
450
750
6
31
51
—
—
—
6
13.8
20.6
200
750
1250
8
31
51
—
—
—
7
13.8
20.6
250
750
1250
10
31
51
—
—
—
—
—
—
300
1000
1500
16
52
86
—
—
—
—
—
—
500
1000
1500
25
69
103
—
—
—
—
—
—
600
1000
1500
34
69
103
—
—
—
—
—
—
667
1000
1500
40
69
103
—
—
—
—
—
—
750
1500
2250
46
69
103
—
—
—
—
—
—
800
1500
2250
60
138
206
—
—
—
—
—
—
850
2000
3000
70
138
206
—
—
—
—
—
—
1000
2000
3000
Table 6. Mechanical Characteristics
Characteristic
Parameter
Mechanical shock
100 G per MIL-STD-202F, Method 213B, Cond. F (at 25 °C)
Vibration
20 G sweep, 10 Hz to 2000 Hz (at 25 °C)
Enclosure rating
per electrical connector type selection (See Figure 3.)
Wetted materials:
port
substrate
adhesives
electronics
304 stainless steel
alumina ceramic
epoxy
glass, silicon
External materials:
housing
connector:
UL 94 HB (standard)
UL 94 V-0 (optional)
cable jacket
304 stainless steel
PBT 30% GF, black
PBT 30% GF, natural (beige)
TPE
Installation torque
per pressure port type (See Figure 4.)
Table 5. Pressure Reference Types
Pressure Reference
Description
Absolute
Output is proportional to the difference between applied pressure and a built-in fixed reference to vacuum (zero pres-
sure), where the minimum operating pressure is set to absolute zero pressure (perfect vacuum).
Sealed gage
1
Output is proportional to the difference between applied pressure and a built-in fixed reference to 1 atmA, where the
minimum operating pressure is set to 14.7 psiA (1 atmA).
Vented gage
2
Sensor measures pressure relative to ambient pressure. Output is proportional to the difference between applied pressure
and atmospheric (ambient) pressure, where the minimum operating pressure is set to atmospheric pressure.
Notes:
1. Sealed gage option only available in pressure ranges at or above 100 psi.
2. Vented gage option only available in pressure ranges between 100 psi and 667 psi (not available on cable harness configurations).