background image

Honeywell Sensing and Control     

5

PX2 Series Heavy Duty Pressure Transducers

ISSUE 8

 

 

50052336

Figure 3. Electrical Connector Type Dimensions (For reference only: mm/[in].)

A

 

Delphi Metri-Pack 150, Standard

(UL 94 HB)

J

Delphi Metri-Pack 150 

(UL 94 V-0)

B

Micro M12 

(IEC 61076-2)

C

DIN

(EN 175301-803C)

Connector:

 DELPHI 12078088

Mating Connector:

 DELPHI 12110192

IP Rating

1

:

 IP65 (all versions)

Connector:

 IEC 61076-2-101

Mating Connector:

 4 POS TYPE D

IP Rating

1

:

 IP65/IP67 (absolute, sealed gage

                         versions)

             IP65 (vented gage versions)

Connector:

 EN 175301-803C

Mating Connector:

 EN 175301-803C DIN

                    43650C 8MM

IP Rating

1

:

 IP65 (all versions)

Pin 

Voltage

Output

Current

Output

Pin

Voltage

Output

Current

Output

Pin

Voltage

Output

Current

Output

A

GND

RTN

1

V+

supply

1

GND

RTN

B

V+

supply

3

GND

RTN

2

V+

supply

C

Vout

NC

4

Vout

NC

3

Vout

NC

PE

NC

NC

1

IP rating is determined by the electrical connector type chosen.

Hole
(vented gage
versions only) 

Hole
(vented gage
versions only) 

Hole
(vented gage
versions only) 

Summary of Contents for PX2 Series

Page 1: ... supply voltage should be set within the range specified for the model 2 Based on the transducer s specified output connect the output lead s to a digital dc or mA meter 3 With no pressure on the transducer turn on the power supply and read the output signal on the voltmeter The reading should correspond to the specification indicated for null offset If not check the connections wire color code an...

Page 2: ...m4 2 kOhm Absolute voltage ratings5 minimum6 maximum6 maximum applied to output pin short circuit protection 7 16 V 16 V Vs 16 V 30 V 16 V 30 V 12 V EMC rating8 CE compliance electrostatic discharge radiated immunity fast transient burst immunity to conducted disturbances radiated emissions 4 kV contact 8 kV air per IEC 61000 4 2 10 V m 80 MHz to 1000 MHz per IEC 61000 4 3 1 kV per IEC61000 4 4 3 ...

Page 3: ...to the product for it to remain in specification once pressure is returned to the operating pressure range Exposure to higher pressure may cause permanent damage to the product 6 Burst Pressure The maximum pressure that may be applied to the product without causing escape of the pressure media The product should not be expected to function after exposure to any pressure beyond the rated burst pres...

Page 4: ...n See Figure 3 Wetted materials port substrate adhesives electronics 304 stainless steel alumina ceramic epoxy glass silicon External materials housing connector UL 94 HB standard UL 94 V 0 optional cable jacket 304 stainless steel PBT 30 GF black PBT 30 GF natural beige TPE Installation torque per pressure port type See Figure 4 Table 5 Pressure ReferenceTypes Pressure Reference Description Absol...

Page 5: ...EC 61076 2 101 Mating Connector 4 POS TYPE D IP Rating1 IP65 IP67 absolute sealed gage versions IP65 vented gage versions Connector EN 175301 803C Mating Connector EN 175301 803C DIN 43650C 8MM IP Rating1 IP65 all versions Pin Voltage Output Current Output Pin Voltage Output Current Output Pin Voltage Output Current Output A GND RTN 1 V supply 1 GND RTN B V supply 3 GND RTN 2 V supply C Vout NC 4 ...

Page 6: ...onnector 24 AWG with TPE jacket Mating Connector Flying leads IP Rating1 IP65 IP67 IP69K absolute sealed gage versions Pin Voltage Output Current Output Wire Color Voltage Output Wire Color Current Output 1 GND RTN red V red supply 2 Vout NC black GND black RTN 3 V supply white Vout Notes 1 IP rating is determined by the electrical connector type chosen 2 Three wire cable is required for ratiometr...

Page 7: ...metry ISO 1179 1 Installation torque1 25 N m 18 4 ft lb Seal2 3 O ring Mating geometry ISO 6149 1 Installation torque1 25 N m 18 4 ft lb N1 1 4 18 NPT N2 1 8 27 NPT Seal pipe thread Mating geometry ANSI B1 20 1 Installation torque1 2 to 3 Turns from finger tight Seal pipe thread Mating geometry ANSI B1 20 1 Installation torque1 2 to 3 Turns from finger tight S1 9 16 18 UNF SAE J1926 3 S2 7 16 20 U...

Page 8: ... 401 Building No 5 JiuGe Business Center Lane 2301 Yishan Rd Minhang District Shanghai China Sales Direct 86 21 6401 6692 Email amall ameya360 com QQ 800077892 Skype ameyasales1 ameyasales2 Customer Service Email service ameya360 com Partnership Tel 86 21 64016692 8333 Email mkt ameya360 com ...

Reviews: