PX2 Series Heavy Duty Presssure Transducers
ISSUE 8
50052336
NOTICE
•
To ensure proper environmental sealing and electrical
connections when using a connector, follow the connector
manufacturer’s installation guidelines.
•
All terminal cavities must be sealed using the correct wire
gauge and seal combination.
•
If only two leads are used, any additional terminal cavities
should be sealed per the connector manufacturer’s
installation guide.
•
Honeywell recommends using a crimping tool for crimping
wires to the connector terminals.
•
Contact the individual connector manufacturer for connector
wiring.
Table 2. Electrical Specifications
Characteristic
Ratiometric Output
Current
Output
Regulated Output
Output Transfer Function Order Code
1
AA
AB
AC
AD
CH
BC
BD
BE
BG
Output transfer function
1
:
null output value
full scale output value
full scale span (FSS)
operating supply voltage, min.(Vs)
2
operating supply voltage, typ. (Vs)
2
operating supply voltage, max. (Vs)
2
10% of Vs
90% of Vs
80% of Vs
4.75 V
5 V
5.25 V
5% of Vs
95% of Vs
90% of Vs
4.5 V
5 V
5.5 V
10% of Vs
90% of Vs
80% of Vs
3.135 V
3.3 V
3.465 V
5% of Vs
95% of Vs
90% of Vs
3.135 V
3.3 V
3.465 V
4 mA
4 mA
16 mA
8 V
—
30 V
4
1 V
6 V
5 V
9 V
—
30 V
3
0.25 V
10.25 V
10 V
13 V
—
30 V
3
0.5 V
4.5 V
4 V
8 V
—
30 V
3
1 V
5 V
4 V
8 V
—
30 V
3
Supply current (typ.)
5 mA
4 mA
—
5.5 mA
Output load (pull up or down)
minimum
maximum
2 kOhm
—
—
(Vs - 8) x
50 Ohm
4
2 kOhm
—
Absolute voltage ratings
5
:
minimum
6
maximum
6
maximum applied to output pin
(short circuit protection)
7
-16 V
16 V
Vs
-16 V
30 V
—
-16 V
30 V
12 V
EMC rating
8
:
CE compliance:
electrostatic discharge
radiated immunity
fast transient burst
immunity to conducted disturbances
radiated emissions
±4 kV contact, ±8 kV air per IEC 61000-4-2
10 V/m (80 MHz to 1000 MHz) per IEC 61000-4-3
±1 kV per IEC61000-4-4
3 V per IEC61000-4-6
40 dB 30 MHz to 230 MHz; 47 dB 230 MHz to 1000 MHz per CISPR 11
ISO 11452-2:
radiated immunity
100 V/m 200 MHz to 2 GHz
20 V/m 200 MHz to 2 GHz
Notes:
1. The Output Transfer Function order code in the catalog listing appears as the last two digits before the final “X”. For example, the “AA” in the
following catalog listing is the transfer function code: PX2BN1XX100PS
AA
X.
2. Transducer will not produce valid output when supply voltage is outside of operating range.
3. Applies at 25 °C. See Figure 2 for Regulated Output Supply Voltage.
4. Applies at 25 °C. See Figure 3 for Current Output Supply Voltage.
5. Absolute maximum ratings are the extreme limits the device can withstand without damage to the product. Voltages above these ratings may
cause permanent damage. Exposure to absolute maximum conditions for extended periods may degrade device reliability.
6. Absolute voltage applies to potential across power and ground terminals.
7. Short circuit protection between output pin and ground, and output pin and supply pin.
8. All EMC ratings verified with the Delphi Metri-Pack 150 electrical connector type.
WIRING INSTRUCTIONS
The wiring code for electrical connection is shown in Figure 3.