UDACT-2 — Instruction Manual
P/N 54089:B3 10/29/2019
7
Section 1: Overview
1.1 Introduction
This document contains information for installing, programming and operating the UDACT-2, Universal Digital Alarm Communica-
tor/Transmitter.
1.2 UL 864 Compliance
1.2.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Sys-
tems, UL 864 10th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications.
Operation of the
UDACT-2 with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest
edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
1.2.2 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features and/or options listed below must be approved by the local AHJ.
1.3 Related Documentation
The table below contains a list of document sources for supplemental information.
Table 1.2 Related Documentation
AM2020/AFP1010
NFS-640
AFP-300/400
NCA
AFP-200
NFS-3030
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as
indicated below.
Program Feature or Option
Permitted in UL 864? (Y/N)
Possible Settings
Settings Permitted in UL 864
AC Loss Reporting Delay
YES
1,2,6,7,8,9,10,11,15,16,17,20, 21,22, 23
hours, and “Immediate” (0)
1 hour
2 hours
Host Panel ID
YES
NFS2-3030
NFS-3030
NCA-2
NCA
NFS2-640
NFS-640
NFS-320
AM2020
AFP1010
AFP-200
AFP-300
AFP-400
NFS2-3030
NCA-2
NFS2-640
NFS-320
Maximum Test Intervals
YES
4, 6, 8, 12, or 24 hours
4 hour or 6 hour
Table 1.1 UL Settings Requirements
Control Panels
Part Number
VeriFire Tools CD help file
AFP-200 Instruction Manual
15511
AFP-300/AFP-400 Installation Manual
50253
NFS-320 Installation Manual
52745
NFS-320SYS Installation Manual
53717
NFS-640 Installation Manual
51332
NFS2-640 Installation Manual
52741
NFS-3030 Installation Manual
51330
NFS2-3030 Installation Manual
52544
AM2020/AFP1010 Installation Manual
15088
NCA Network Control Annunciator
51482
NCA-2 Network Control Annunciator
52482
Notifier Device Compatibility Document
15378