Maintenance Programming Level
Programming
3.7 Maintenance Programming Level
To access Maintenance Programming mode, press the
Enter
key. The LCD will display the following:
To enter the Maintenance Programming mode, press
2
. The display will read as follows:
When the
Maintenance
level password (default
11111111
) is entered, the following screen will appear:
Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the
keypad
down
arrow key, as shown in the following screen.
3.7.1 Disable Point
Pressing
1
for Point Program, while viewing Maintenance Screen #1 will cause the following screens to be
displayed:
Select the device type by pressing
1
for an addressable detector or
2
for an addressable module. The operator will be prompted to enter
the three digit device address as shown in the following example for a detector:
A flashing cursor will appear in the bottom left corner of the display, prompting for the three digit device address. When the third digit is
enter,
001
for example, a screen will appear which will allow enabling or disabling of the selected point, as illustrated in the following
example:
Pressing
1
repeatedly will cause the display to toggle between
Enabled Yes
and
Enabled No
.
3.7.2 History
Pressing
2
while viewing Maintenance Screen #1 will cause the following screen to be displayed:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FSTOOL UP/DOWNLOAD
4=USB UP/DOWNLOAD
PROGRAMMING
ENTER PASSWORD
MAINT PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
MAINT PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
POINT PROGRAM
1=DETECTOR
2=MODULE
Device Select Screen
EDIT DETECTOR
ENTER POINT ADDRESS
Address Select Screen
EDIT DETECTOR 1D001
1=ENABLED YES
Enable/Disable Select Screen
MAINT PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen