Master Programming Level
Programming
Since the options for each of these module types can be individually set, pressing
2
for
Module Options
, while viewing the ANN-BUS
Address Screen will display the available options as described below.
ANN-I/O Options
Pressing
2
for Module Options while viewing ANN-BUS Address screen when the ANN-I/O option is selected will display the follow-
ing screen:
Pressing
1
while viewing the ANN-I/O Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information. Each press of the 1 key will toggle the display between
Zone
and
Point
.
Pressing
1
while viewing the ANN-I/O Address Screen #3 will select the Point range to be annunciated (refer to the tables in “
” on page 89). If Point has been selected, each press of the
2
key for
Range
will
change the points to be annunciated with the options being 001 - 030 and 031 - 050.
Pressing
2
while viewing ANN-I/O Address Screen #3 will select either addressable detectors or addressable modules to be annunciated.
ANN-I/O - ADDR X-1
SLC 1 DET 001-030
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
ANN-I/O - ADDR X-1
1=POINT/ZONE POINT
ANN-I/O Address Screen #2
ANN-I/O - ADDR X-1
1=RANGE PT001-030
2=DET/MOD DET
ANN-I/O Address Screen #3